ACK
XXXXXX
Selection: -999999 to 999999
MENU
FnrL1
Function of the relay SP1
ACK
OPEN
Selection between OPEN or CLOSE at the alarm conditions
MENU
SP 2
Set Point SP2
ACK
XXXXXX
Selection: -999999 to 999999. The relay is activated when the display
arrives at the SP1 or higher values
MENU
HSt 2
SP2 Hysterese
ACK
XXXXXX
Selection: -999999 to 999999
MENU
FnrL2
Function of the relay SP2
ACK
OPEN
Selection between OPEN or CLOSE at the alarm conditions
Options SP3 and SP4 are configured as SP1 and SP1.
MENU
Aout L
Display value for Analog Output 0 (-10) V and 0/4mA
MENU
Aout H
Display value for Analog Output 10V and 20mA
The Output 0-10V or -10…10V are jumper selectable
MENU
SEt SEn
Selection of the type of linearization
LinEAr
linear type of characteristic for DC- and AC inputs.
POLYn Polynom
Linearizing
tAbtAb
X-Y Table assignement of input signal to display reading
Pt
100
RTD
thermometer
tEr3t
Thermistor 9796 Ohm @ 0 ºC
tEr5t9
Thermistor 27936 Ohm @ 0 ºC
tC E
Thermocouple E with external could junction
tCC E
Thermocouple E with internal could junction
tC J
Thermocouple J with external could junction
tCC J
Thermocouple J with internal could junction
tC L
Thermocouple K with external could junction
tCC L
Thermocouple K with internal could junction
tC S
Thermocouple S with external could junction
tCC S
Thermocouple S with internal could junction
tC b
Thermocouple B with external could junction
tCC b
Thermocouple B with internal could junction
tC t
Thermocouple T with external could junction
tCC t
Thermocouple T with internal could junction
tC C
Thermocouple C with external could junction
tCC C
Thermocouple C with internal could junction
Cold
Cold junction temperature measured and displayed
MENU
Set in
0.0 1
Setting for bipolar inputs, e.g. ±1V and 0-20mA
0.2 1
Setting for shifted inputs, e.g. 4-20mA.
-1 1
Setting for bipolar input signals, e.g. –20 ... +20V.
MENU
Set LO
Required display value for the minimum input signal (e.g. 4mA)
MENU
Set HI
Required display value for the maximum input signal (e.g. 20mA)
MENU
bAUd
Baud rate of the data port
ACK
1200
Selection: 1200 to 19200 bd
MENU
Contin
Transmission Mode
ACK
OFF
On = continuous transmission, OFF=request transmission
MENU
rS Adr
Address of the RS485 data port
ACK
rS 232
RS232 is activated with address 00
31
RS485 is activated with one of addresses 01 … 31
MENU
StPASS
Password selection from 20 stored combinations
MENU Start
Measuring
mod
8