SERVICE MENU - HtESt 

 
The Service Menu 

HtESt

 permits fast check of the instrument’s performance and offers the software 

calibration via the keyboard. To enter the Service menu, keep the key 

MENU

 pressed while the 

instrument is switched-on. Release the key when the display shows 

HtESt

. The service menu steps are 

incremented forward with the key 

MENU

, decremented backward with 

SET

.  

 
In the service menu the digit segments are tested first. After the HCF value can be entered (see bellow). 
Than the signal channel can be calibrated. The set point relays and the display LEDs are activated. At 
the end the analog outputs are generated.   
 

Segments

 

all segments are activated 

HCF.128

 

HCF parameter defines the range of the menu. The menu without options Analog Output, 
Set Points and RS data ports is determined with HCF = 128. Each option is activated in 
the menu with binary value added to the HCF 128: 
1 SP1 
2 SP2 
4 SP3 
8 SP4 
16 Analog 

output 

32 Baud 

rate 

64 

Address of the data port 

Combinations define the menu range:  
HCF.144    Menu (128) and Analog Output (16). 
HCF.240    Menu (128), Analog Output (16), Baud rate (32) and Address (64). 

AdC 

   

ADC internal DC value of the converter.  

 

 

ATTENTION!

  The input signal has to be set to ZERO before this Step is entered!

 

1.25XXX 

Apply the zero signal value. The display shows the internal voltage reference 1.25V. 

 

 

 

The Zero Value will be calibrated when the key 

DOWN

 is pressed. The display shows  

Ac LO

. Press the key 

ACK

 and keep it pressed until the display shows 

EE StO

.  

The Zero Signal Value has been calibrated. 
 

2.2XXXX

 

The Maximum Signal Value will be calibrated when the full range signal is applied and the 

 

 

key 

UP

 is pressed.  The display shows 

AC HI

. Press the key 

ACK

 and keep it pressed  

until the display shows 

EE StO

.  

The maximum signal value has been calibrated.  

 

rES

 

 

The Display shortly shows 

rES 

and switches into the measuring mode. The display  

corresponds to the 

SEt HI

 programmed value in the main menu. 

 

COL. X

 

Correction of the cold junction temperature. 

 

SP1

 

 

Set Point 1 and the Relays 1 are activated. 

SP2

 

 

Set Point 2 and the Relays 2 are activated. 

SP3

 

 

Set Point 3 and the Relays 3 are activated. 

SP4

 

 

Set Point 4 and the Relays 4 are activated. 

An - 10

 

Analog Output -10V and 0/4 mA are generated (0 or 4mA selectable). 

An - 5 

 

Analog Output -5V and 5/8 mA are generated. 

An    0

  

Analog Output   0V and 10/12 mA are generated. 

An    5 

 

Analog Output   5V and 15/16 mA are generated. 

An   10

 

Analog Output 10V and 20 mA are generated. 

StArt  

Measuring Mode 

 12

Содержание OC 7040A

Страница 1: ...OC7040A_GB_21002 Process Controller OC 7040A Owner s Manual ORBIT CONTROLS AG Zürcherstrasse 137 CH 8952 Schlieren ZH Tel 41 44 730 2753 Fax 41 44 730 2783 info orbitcontrols ch www orbitcontrols ch ...

Страница 2: ...2 ...

Страница 3: ...portgesellschaft unterschreiben lassen Bewahren Sie bitte das Verpackungsmaterial für eventuelle Reklamationen auf Unpacking Instructions Remove the Packing List and verify that you have received all equipment including the following Orbit Controls Model OC 7040A Programmable Controller Operator s Manual OC 7040A If you have any questions about the shipment please call the Orbit Controls Customer ...

Страница 4: ...s 9 5 5 Strain Gauge with Current Supply 9 5 6 Strain Gauge with Voltage Supply 9 5 7 Range Selection 10 5 8 Supply Voltage Selection 115 230VAC 11 6 SERVICE MENU HtESt 12 7 CALIBRATION 13 7 1 Calibration of linear Signals DC and AC 13 7 2 calibration of non linear Signals Tables 13 7 2 1 Calibration of Pt 100 Thermometers 13 7 2 2 Calibration of Thermocouples 13 7 3 Calculation of R19 13 8 BURST ...

Страница 5: ...et points and assignment of the input signal to the display A Tara function is available for setting the display to zero at any measuring point For supplying of external sensors an adjustable Excitation is available Service Menu HtESt is suitable for checking of the instrument s performance and the calibration 1 KEYBOARD Key Function in Measuring Mode UP Maximum stored value appears at the display...

Страница 6: ...00 1 C 1 digit T C Thermis 2 C 1 digit Tempco 25 ppm C Set Points Standard Set Point Relay SP1 SP2 5A 230VAC Option Additional Relays SP3 SP4 5A 230VAC Setting range 999999 Each Set Point has adjustable Hysterese from 0 to 99 Analog Output Option Analog Outputs 0 4 20mA and 0 10V 12 bit resolution Option 16 bit Isolation 250V RMS Data Output Option RS232 or RS485 with addresses 01 31 8 bit 1 Start...

Страница 7: ...WN MENU OrdEr Decimal Point Display Resolution ACK CCCC dd Select with UP or DOWN MENU Fn tArA Tara function OFF ONLY or ON ACK ONLY After pressing the key SET the display will be forced to zero ON The key SET pressed once forces the display to zero When pressed for second time the display returns to the non tare original signal value MENU FiltEr Setting of filter constant averaging filter type AC...

Страница 8: ...tion tCC J Thermocouple J with internal could junction tC L Thermocouple K with external could junction tCC L Thermocouple K with internal could junction tC S Thermocouple S with external could junction tCC S Thermocouple S with internal could junction tC b Thermocouple B with external could junction tCC b Thermocouple B with internal could junction tC t Thermocouple T with external could junction...

Страница 9: ...5 CONNECTIONS EXAMPLE 5 1 Process Signal 0 4 20mA 5 2 Two Terminal Sensor 5 3 RTD Thermometer and Ohmmeter 5 4 Thermocouples and Thermistors 5 5 Differential input 5 6 Strain Gauge with voltage supply 9 ...

Страница 10: ...V 100V 10mV 1V H1 1 2 1 2 2 3 2 3 1 2 Z8 Z9 DC Z8 close Z9 open AC Z8 open Z9 close H3 1 2 2 3 R19 page 11 7 3 open open open open R 50k G 1 Input single ended 15 14 13 15 14 13 15 14 13 15 14 13 15 14 13 Input differential 15 13 15 13 10 ...

Страница 11: ...5 8 Supply Voltage Selection115 230VAC Solder Side of the Printed Board 115VAC X2 X3 closed 230VAC X1 closed X1 open X2 X3 open 11 ...

Страница 12: ... DC value of the converter ATTENTION The input signal has to be set to ZERO before this Step is entered 1 25XXX Apply the zero signal value The display shows the internal voltage reference 1 25V The Zero Value will be calibrated when the key DOWN is pressed The display shows Ac LO Press the key ACK and keep it pressed until the display shows EE StO The Zero Signal Value has been calibrated 2 2XXXX...

Страница 13: ... the Menu Switch into the measuring mode with ACK The Display follows the temperature of the selected T C within its defined range The cold junction is compensated with SMT160 connected to the terminal block 7 3 Calculation of R19 When the individual measuring range by using R19 is selected following has to be considered The AD C type LT2400 is designed for bipolar operation Its zero reference poi...

Страница 14: ...de Linear Set LO 000000 Set HI 10000 Input 4 20mA Display 10 000 8 1 Test Conditions According to IEC 801 4 IEC 1000 4 4 EN 50052 1 8 2 Test Set Up 8 3 Test Results Zone 1 2kV Burst Display 10 000 without change Zone 2 2kV Burst Display 10 000 without change CE Approval No 321 30 3 539 c j 9004 69 from 15 6 1998 VTUE Praque 14 ...

Отзывы: