Install the SAS Drive Signal Cable
“Component Service Task Reference” on page 47
.
Related Information
■
“Install the SAS Drive Signal Cable” on page 197
■
“Component Locations (Storage, Power, NVMe, and Fan Modules)” on page 14
■
“Component Locations (Motherboard, Memory, and PCIe Cards)” on page 16
■
“Preparing for Service” on page 43
■
“Returning a Server to Operation” on page 235
Install the SAS Drive Signal Cable
Installing a cable is a cold-service operation. You must power off the server before installing the
cable.
1.
If replacing a faulty cable, fold the new cable with 90-degree bends on each end.
2.
Route the cable into the cable pass through:
Caution -
The cable pass through is fragile. Take care not to torque or stress it, which could
cause damage.
Servicing the Cables
197
Содержание Netra SPARC S7-2
Страница 1: ...Netra SPARC S7 2 Server Service Manual Part No E73207 03 February 2017 ...
Страница 2: ......
Страница 12: ...12 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 24: ...24 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 42: ...Server Fault Remind Button Operation 42 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 84: ...84 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 108: ...108 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 140: ...140 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 150: ...150 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 158: ...158 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 192: ...192 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 216: ...216 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 258: ...258 Netra SPARC S7 2 Server Service Manual February 2017 ...