Install the Storage Server Into the Slide-Rail Assemblies
■
“Mark the Rackmount Location” on page 31
■
“Install the Storage Server Into the Slide-Rail Assemblies” on page 38
Install the Storage Server Into the Slide-Rail Assemblies
Use this procedure to install the storage server chassis, with mounting brackets, into the slide-
rail assemblies that are mounted to the rack.
Caution -
This procedure requires a minimum of two people because of the weight of the
storage server. Attempting this procedure alone could result in equipment damage or personal
injury.
Caution -
Extend your rack's anti-tilt bar to prevent the rack from tipping during equipment
installation.
1.
Push the slide-rails into the slide-rail assemblies in the rack as far as possible.
2.
Position the storage server so that the rear ends of the mounting brackets are
aligned with the slide-rail assemblies that are mounted in the rack.