4.2 PV200 Power, Petro-Net
Shared and Separate Conduit
Shared Terminal Power Conduit
This conduit should run from the main circuit panel to each Terminal and can be looped from terminal to
terminal. This conduit should only contain the Terminal Feed, Terminal Neutral and Ground wires, with the
exceptions noted below.
Terminal Power and Petro-Net Wiring Requirements
Terminal Feed
Minimum #14 AWG Stranded (Black) – Oil/Gas resistant, Wet Locations
Terminal Neutral
Minimum #14 AWG Stranded (White) – Oil/Gas resistant, Wet Locations
Terminal Ground
Minimum #14 AWG Stranded (Green) – Oil/Gas resistant, Wet Locations
Petro-Net (RS-485)*
Two (2) #18 AWG twisted (10 per ft) pair – 600V-rated – Oil/Gas resistant,
Wet Locations
*NOTE: Petro-Net wiring can share terminal power conduit when the Petro-Net cable voltage insulation rating is 600V.
Separate Terminal Power Conduit
Doc. No.: M1010 Rev.: 10
Page 24 of 98