4.3 Tank Alert Installation
The Tank Alert can be installed in a building or an outdoor location.
Two (2) #8 x 1.25 self-tapping screws and sealing washers are included with the Tank Alert. Select an
installation location over a wall stud or use wall anchors. The illustration below shows the installation screw
hole locations.
Drill holes of the correct size for an applicable conduit.
IMPORTANT:
Be careful to not cause damage to internal components when you drill holes
for conduit.
Attach the conduit to the Tank Alert enclosure. Apply a sealant around the conduit(s) to keep gases or fluids
out of the enclosure.
4.4 Tank Alert Wiring
NOTE:
Refer to the M2018 Nano Field Wiring Diagram for wiring connections inside the Tank
Alert enclosure.
IMPORTANT:
Use a minimum gauge 14 AWG stranded copper wire.
See the connection diagram below for relay (internal or OM4) and power connections to the Tank Alert.
Doc. No.: M2010-EU Rev.: 13
Page 31 of 149
Содержание M2010-EU
Страница 6: ...Warranty 147 Doc No M2010 EU Rev 13 Page 6 of 149...
Страница 20: ...Main Board Connections Jumpers and LEDs Doc No M2010 EU Rev 13 Page 20 of 149...
Страница 21: ...Conduit Installation Doc No M2010 EU Rev 13 Page 21 of 149...
Страница 22: ...Field Wiring Diagram Doc No M2010 EU Rev 13 Page 22 of 149...
Страница 32: ...Doc No M2010 EU Rev 13 Page 32 of 149...
Страница 38: ...924B Probe Installation DMP Probe Installation Doc No M2010 EU Rev 13 Page 38 of 149...
Страница 41: ...Doc No M2010 EU Rev 13 Page 41 of 149...
Страница 86: ...Typical Installation Drawings 30 0230 S Doc No M2010 EU Rev 13 Page 86 of 149...
Страница 110: ...Appendix C Declaration of Conformity Doc No M2010 EU Rev 13 Page 110 of 149...
Страница 111: ...Doc No M2010 EU Rev 13 Page 111 of 149...
Страница 112: ...Doc No M2010 EU Rev 13 Page 112 of 149...
Страница 113: ...Doc No M2010 EU Rev 13 Page 113 of 149...
Страница 142: ...Doc No M2010 EU Rev 13 Page 142 of 149...
Страница 146: ...Doc No M2010 EU Rev 13 Page 146 of 149...
Страница 149: ......