background image

OPW 1-3100 Series Spill Container 

 

Page 27 

1-3100 SERIES ELECTRONIC SENSOR 
REPLACEMENT INSTRUCTIONS 
(Only applies to 1-3122 & 1-3132 models) 
 
Step 1: 

 (See Figures 1 & 4)

 

Remove the white sensor adaptor from primary 
bucket and pull sensor to grade.  Be careful not to 
damage sensor. 

 
Step 2: 

 

Ensure that the old sensor is not functional.  Test the 
sensor by flipping it over and checking for an alarm.  
Alternate test method: Dip the sensor in a cup of 
water and check for an alarm. 

 
Step 3:

  

Near the old sensor, cut the sensor wire.  Discard 
the old sensor. 
 

Step 4:

 (See Figure 1)

 

Verify that the factory installed loop in the sensor 
wire is 10-

1/2” tall from the bottom of the sensor to 

the top of the loop as shown in Figure 1.  Cut new 
sensor wire 2 feet from the sensor loop.  
Note: Splice is to be installed no closer than 2 feet 
from the sensor loop.   
Note: At least 4 feet of wire should be between the 
sensor and the grommet. 
 

Step 5:  

(See Figure 2) 

Remove the end caps from the splice kit barrel. 
Cut the tip off of one of the cones on each of the end 
caps so that the end cap will fit snugly around the 
sensor wiring. 
 

 

Figure 2 

 

Step 6:

 (See Figure 3) 

Insert the new sensor wire through the hole in one of 
the end caps and the existing sensor wire (coming in 
thru the secondary base) through the hole in the 
other end cap and slide the end caps out of the way.  
Slide barrel and sleeve onto the sensor wire and 
slide out of the way as shown in Figure 3. 

 

Figure 3 

 

Step 7: 

Using the included wire nuts, join the wires per the 
sensor manufacturer’s instructions. Using the 
included split bolt, securely fasten the two wire ends 
together.  
 

Step 8: 

Center the barrel and sleeve over the splice and 
slide end caps onto the barrel. 
 

Step 9: 

Warm the included compound to at least 60° F (15° 
C).  As shown in the compound mixing instructions, 
break the center barrier in compound bag by 
grasping the sides of the bag and rolling thumbs 
through the barrier.  Thoroughly mix the compound, 
being sure to strip the compound from the corners 
while mixing. 

 
Step 10: 

Cut one corner off of bag and pour the compound 
through the opening in the barrel until completely 
full. 
 

Step 11: 

Close the barrel by centering the sleeve over the 
hole in the barrel and rotating the sleeve around the 
barrel until the hole is completely covered 
 

Step 12: 

Test the sensor by flipping it over and checking for 
an alarm. Alternate test method: Dip the sensor in a 
cup of water and check for an alarm. 
 

Step 13: 

(See Figures 1 & 4) 

Wait at least 5 minutes then feed the splice kit and 
excess wire into the secondary bucket.  Align sensor 
with the hole in the primary base where the sensor 
adaptor will be installed as shown in Figures 1 & 4.  
Ensure sensor is as flat as possible on bottom of 
secondary base.  Inspect o-ring on sensor adaptor 
replace if it is not in good condition.  Thread sensor 
adaptor back into primary bucket until o-ring is no 
longer visible (approximately 6 turns), do not 
overtighten. 

 
Step 14:

 

 

Test bucket as indicated in Step 9 of Installation 
Instructions. 

End 
Cap 
 
Barrel 
 
 
 
Sleeve 
 
 
 
 
 
End 
Cap 

Existing sensor wire 

New sensor wire 

Отзывы: