34
-
4.11.5 Diagnoses alarm
The diagnoses alarm for Optris0A90 is set up as follows:
Byte
Data
Description
0x00
0x06
Header
0x01
0x01
Diagnoses alarm
0x02
0x00
Head station
0x03
0x00
0x01 : Coming result
0x02 : Leaving result
0x04
Error
Bit 0: Assembly group disruption
Bit 1: Internal error
Bit 2: External error
Bit 3: Channels
0x05
0x03
Number of channels
0x06
Bit 0: Diagnoses result at channel 0
Bit 1: Diagnoses result at channel 1
Bit 2: Diagnoses result at channel 2
0x07
Channel 0
– Box
0x08
Channel 1
– Sensing head
0x09
Channel 2
– Target
Содержание PROFIBUS-DP-V1
Страница 1: ...Operator s Manual optris PROFIBUS Interface for optris CT infrared thermometers...
Страница 15: ...PROFIBUS DP 15 4 5 State machinery within the slave...
Страница 20: ...20...
Страница 36: ...optris PROFIBUS MA E2021 03 A...