For a usage of the CS for online maintenance applications (in electrical cabinets e.g.) the following recommend
settings are already included in the factory default setting (but not active):
OUT
At 3-state output the following settings are default:
Pre-alarm
difference:
2
°C
No alarm level:
8 V
Pre-alarm level:
5 V
Alarm level:
0 V
Service
voltage:
10
V
IN/
OUT: At
Alarm output (open collector) the following settings are default:
Mode:
normally closed
Temp code output:
activated (for values above alarm level)
Range settings:
0 °C = 0 %/ 100 °C = 100 %
Vcc
adjust:
If
activated the following settings are default:
Output
voltage
range:
0-10
V
Difference mode:
activated
optris CS – E2010-12-A
5
Alarm level
Alarm value (IN/ OUT pin)
Vcc
1
40 °C
11 V
2
45 °C
12 V
3
50 °C
13 V
4
55 °C
14 V
5
60 °C
15 V
6
65 °C
16 V
7
70 °C
17 V
8
75 °C
18 V
9
80 °C
19 V
10
85 °C
20 V