Understanding the Features
3--7
The following describes the function of each of the registers shown in the table.
S
Register M+0
-- Field point 1 data. Either setpoint or display, as
configured. Numeric data is either a Binary value or the
four least significant digits of the BCD long number in
field point 1.
S
Register M+1
-- Field point 1 data cell 2 (for long BCD numbers only).
Either setpoint or display, as configured. Numeric data
is the four most significant digits of data for field point 1.
S
Register M+2
-- Field point 2 data.
S
Register M+3
-- Field point 2 data cell 2 (for long BCD numbers only).
S
Register M+4
-- Field point 3 data.
S
Register M+5
-- Field point 3 data cell 2 (for long BCD numbers only).
S
Register M+6
-- Field point 4 data.
S
Register M+7
-- Field point 4 data cell 2 (for long BCD numbers only).
S
Register M+8
-- Field point 5 data.
S
Register M+9
-- Field point 5 data cell 2 (for long BCD numbers only).
S
Register M+10
-- Field point 6 data.
S
Register M+11
-- Field point 6 data cell 2 (for long BCD numbers only).
S
Register M+12
-- Field point force data. Value to force setpoint equal to
when force operation is initiated by the PLC program.
S
Register M+13
-- Field point force data cell 2 (for long BCD numbers
only). Four most significant digits of BCD long value to
force setpoint equal to when force operation is initiated
by the PLC program.
S
Register M+14
-- Force control. Controls the forcing of setpoints.
>
FSP
bit: When set, the field point force data (M+12
and/or M+13) will be forced into the field points that are
set to be forced selected by FP1--FP6. Once the force is
finished, the OP--414 will clear M+12, M+13 and M+14.
>
FP1--FP6
bits: Identifies the setpoints to be forced.
Register Definition