background image

 

7

p

 

OUTPUT POWER RECEPTACLES 

 

q

 

AC INPUT POWER RECEPTACLE 

r

 INPUT CIRCUIT BREAKER 

It trips when the connected loads exceed the protected receptacle‘s capacity, The center 
plungers of the circuit breakers extend when tripped. 

 

s

 RS232 INTERFACE 

Provide both RS-232 and relay signal to support NOVELL, UNIX, DOS, WINDOWS and 
other operating systems. 

 

t

 

SNMP INTERFACE PORT (optional) 

Provide the SNMP adapters for 10-BaseT Ethernet and Token Ring connectors. Through the 
SNMP adapter, your UPS becomes “SNMP manageable”. It provides a real time UPS and 
power status information for the network manager.     

CAUTION

: Use only factory supplied or authorized SNMP monitoring cable! 

 

_

 

USB INTERFACE 

Provide USB signal to support WINDOWS 98SE/Windows 2000/Widnows XP/Windows 
NT4.0 operating systems. 

 

 

 

 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 

Содержание Power PS1000C

Страница 1: ...1 User Guide Power Series Models PS1000C PS1250C PS1500C PS2000C PS3000C ...

Страница 2: ...g of fuse WARNING Intend for installation in a controlled environment CAUTION Do not dispose of batteries in a fire the battery may explore CAUTION Do not open or mutilate the battery released electrolyte is harmful to the skin and eyes CAUTION A battery can present a risk of electric shock and high short circuit current The following precaution should be observed when working on batteries Remove ...

Страница 3: ...the UPS for service Damage happened during transit is not covered under the warranty Intelligent microprocessor control The product is an advanced line interactive UPS based on microprocessor control This means that it operates with the newest technology high performance and powerful function The line interactive UPS is an intelligent protector and provides pure reliable AC power to the critical l...

Страница 4: ...g software optional kits make your computer operate intelligent and provide you with the ability of perfect protection of your critical devices The software is available for most operation systems and is supplied with a communication cable that connects to the UPS Note There is no guarantee that interference to radio TV will not occur in a particular installation If this UPS causes interference to...

Страница 5: ...n replace battery disconnect the utility power then open the case and take notice of the battery s polarity while install the new battery to avoid short circuit r BUCK AVR VOLTAGE REDUCTION indicator YELLOW LED The LED illuminates when the UPS is correcting a high utility voltage condition The loads receive normal power s LINE NORMAL indicator GREEN LED The LED illuminate when the line input volta...

Страница 6: ...no 2 Light no 1 of Bat Level over 91 76 90 51 75 26 50 0 25 1 3 Rear Panel For 1 2KVA For 3KVA n TEL MODEM connector Telecom transfer ports provide users to extend the applications CAUTION To reduce the risk of fire use only No 26AWG or larger telecommunication line cord oEXTERNAL BATTERY PACK CONNECTOR optional CAUTION Use only factory supplied or authorized connecting cable for external battery ...

Страница 7: ...ort NOVELL UNIX DOS WINDOWS and other operating systems t SNMP INTERFACE PORT optional Provide the SNMP adapters for 10 BaseT Ethernet and Token Ring connectors Through the SNMP adapter your UPS becomes SNMP manageable It provides a real time UPS and power status information for the network manager CAUTION Use only factory supplied or authorized SNMP monitoring cable _ USB INTERFACE Provide USB si...

Страница 8: ... battery pack optional Before connecting make sure the external battery pack and the connector cable are compatible Note External battery connection is not necessary The UPS works properly without external battery pack connection Except AL models only CAUTION Use only factory supplied or external battery connection cable 2 4 Charge the battery The UPS charges its battery whenever it is connected t...

Страница 9: ...ing 3 4 Self test Use the self test to verify both the operation of the UPS and the condition of the battery In normal utility power push the ON TEST button more than 1 second and UPS performs a self test function During the self test the UPS operates a back up mode Note During the self test the UPS briefly operates the loads on battery the on battery LED comes on If the UPS passed the self test i...

Страница 10: ...mes to lower level about 20 30 The UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to LINE mode operation Attention The alarm of the batteries caused by low voltage beeps every second Fast speed beep Attention The rapid alarm under LOW BATTERY condition can t be erased When the UPS is working under overload condition the connected loads exceed the maximum rated capaci...

Страница 11: ...shown in Fig 5 1 Please select the operating system applied for your computer and then click on it For example if your operating system is Windows 98 please click select item Windows 95 98 Me 2000 NT XP Note If the installation program doesn t start automatically select StartÎProgramsÎWindows Explorer for Windows 98 and then double click on the setup icon in your CD ROM drive as shown in picture 5...

Страница 12: ...ORT at computer side can be either COM 1 COM 2 COM 3 COM 4 or USB CAUTION Use only factory supplied or authorized UPS monitoring cable 5 4 The characteristics of software SENTINEL The communication port on the back of the UPS may be connected to host computer Through utilizing SENTINEL software the computer is allowed monitor the status of the UPS and control the operation of the UPS in some cases...

Страница 13: ...hown in Fig 5 6 Fig 5 6 The main menu contains tools and feather for monitoring UPS operation and controlling UPS For details on each tool and function of SENTINEL please click on Help button on main menu of SENTINEL as shown in Fig 5 7 Fig 5 7 ...

Страница 14: ...e computer interface port to avoid unnecessary draining the battery 6 3 To extend the storage 6 3 1 During the environment where the ambient temperature is 15 to 30 5 to 86 charge the UPS s battery every 6 months 6 3 2 During the environment where the ambient temperature is 30 to 45 86 to 113 charge the UPS s battery every 3 months 7 BATTERY AND BATTERY CABINET 7 1 Battery s life of UPS The batter...

Страница 15: ...failure Contact the dealer or service center for help Buzzer keeps beeping Overload Take off some load There is an open circuit on UPS input protector Move the Input Non fuse switch back to its normal position re engage UPS Utility Indicating light is shining The voltage of utility is exceeding UPS input range Save the digital data and shutdown the applying program to make sure utility is within U...

Страница 16: ...tomatic shutdown if overload exceeds 110 of nominal at 20 second and 125 at 2 seconds Transfer Time 6 8 milliseconds typical including detection time Protection and Filtering Short Circuit UPS output cut off immediately or input circuit breaker protection Type Hot swappable Sealed Maintenance free lead acid with 3 6 years lifetime Typical Recharge Time 4 hours to 90 of full capacity Protection Aut...

Страница 17: ...nal from computer SNMP Slot Yes Ambient Operation 3 500 meters max elevation 0 95 humidity non condensing Temperature 0 40ºC Audible noise 45dBA 1 meter from surface Environment Storage condition 15 000 meters max elevation Note Characteristics are subject to change without prior notice ...

Отзывы: