PS1000B / PS1500B/ PS2200B / PS3000B 

 

 

 

MODEL: PS1000B-RM, PS1500B-RM

 

 

100V/110V/120V

 

PS2200B-RM, PS3000B-RM 

 

220V/230V/240V

 

2.2   On Button 
 

1. 

When the UPS is off and AC power is present, press the On button for 1~2 
seconds to turn on the UPS. 

 

 

UPS can be turned on even when AC power is not present.

 

 
2. 

Pressing the On Button when AC power is available causes the UPS to test 
itself by switching to its internal battery for a few seconds.  We recommend 
you close all your open files before initiating this test.

 

 
3. 

If AC power fails, the UPS warns you with an audible alarm. To silence the 
alarm, press the On Button. When the battery starts to get low, the audible 
alarm will return and beep faster.

 

 

2.3 Off Button 

The Off Button has two steps to shutdown UPS : 
 

1.  

Pressing the Off Button when AC power is available causes the UPS 
into the sleep mode. We recommend you close all your open files before 
initiating this test.

 

2.  

Pressing the Off Button 3 seconds when AC power fails causes the UPS 
into sleep mode. Then pressing the Off Button 3 seconds causes the 
UPS to shutdown completely.

 

Содержание Line Interactive UPS Series PS1000B-RM

Страница 1: ...User Guide Power Series Models PS1000B PS1500B PS2200B PS3000B PS1000B RM PS1500B RM PS2200B RM PS3000B RM ...

Страница 2: ......

Страница 3: ...emarks of OPTI UPS Corporation For your records The serial number of your UPS is on the rear panel You should note the serial number in the space provided below Retain this booklet as a permanent record of your purchase to aid in identification in the event of theft or loss Model No Serial No Purchase Date ...

Страница 4: ...y does not cover 1 Any product on which the serial number has been defaced modified or removed 2 Damage deterioration or malfunction resulting from a Accident misuse neglect fire water or other acts of nature unauthorized product modification or failure to follow instructions supplied with the product b Repair or attempted repair by anyone not authorized c The fault is result of accidental damage ...

Страница 5: ...plied warranties and or do not allow the exclusion of incidental or consequential damages so the above limitations and exclusions may not apply to you Limitations of Warranty for Australian States and Territories The Trade Practices Act 1974 and corresponding State and Territory Fair Trading Acts or legalization of another Government the relevant acts in certain circumstances imply mandatory condi...

Страница 6: ...ORT CIRCUIT CURRENT FIRE OR EXPLOSION FROM VENTED GASES OBSERVE PROPER PRECAUTIONS WHEN REPLACING BATTERIES USE THE SAME NUMBER AND THE FOLLOWING TYPE BATTERIES SEALED LEAD ACID MAINTENANCE FREE PS1000B 1234W x2 PS1500B 1234W x3 PS2200B 7 2AH 12V x8 PS3000B 1234W x8 PS1000B RM 7 2AH 12V x3 PS1500B RM 1234W x3 PS2200B RM 1221W x8 PS3000B RM 1221W x8 PROPER DISPOSAL OF BATTERIES IS REQUIRED REFER TO...

Страница 7: ...cles Do not place the UPS under direct sunshine or close to heat emitting sources This UPS is intended for installation in a temperature controlled indoor area free of conductive contaminants The socket outlet shall be installed near the UPS and easily accessible With the installation of the UPS it should be prevented that the sum of the leakage current of the UPS and the connected consumer exceed...

Страница 8: ...tion which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and the receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an ...

Страница 9: ...pacity bar graph 7 2 7 Fault code 7 2 8 Status Indication 7 2 9 Communication Port 8 2 10 Start Up On Battery 8 2 11 Data Line Surge Suppression 8 3 INSTALLATION AND OPERATION 3 1 Unpacking and Inspection 9 3 2 Placement 9 3 3 Determining How Much Equipment You Can Connect to Your UPS 9 3 4 Powering Up Your UPS 10 3 5 Connecting Your Equipment to the UPS 10 3 6 Operation and Functional Test 12 3 7...

Страница 10: ... that your equipment gets from the wall outlet This provides guaranteed compatibility with all types of loads and even the most sensitive equipment 1 3 Smart Buck and Boost Line Conditioning The voltage from your AC power source can fluctuate above and below the standard rating This microprocessor controlled UPS provides line conditioning via both buck step down voltage and boost step up voltage f...

Страница 11: ...ther with software also provide you with important operating information From your computer screen you can know input output voltage and current frequency battery voltage etc and analyze power problems If software is not part of your UPS package you can purchase it from your local dealer 1 6 Schedule Shutdown Startup Using software you can locally or remotely control the shutdown and startup of eq...

Страница 12: ...4 PS1000B PS1500B PS2200B PS3000B 2 UPS CONTROLS 2 1 External Views MODEL PS1000B PS1500B PS2200B PS3000B Front Panel MODEL PS1000B RM PS1500B RM PS2200B RM PS3000B RM PS1000B PS1500B PS2000B PS3000B ...

Страница 13: ...PS1000B PS1500B PS2200B PS3000 5 Rear Panel MODEL PS1000B 100V 110V 120V 220V 230V 240V MODEL PS1500B 100V 110V 120V 220V 230V 240V MODEL PS2200B PS3000B 100V 110V 120V 220V 230V 240V 100V 110V 120V ...

Страница 14: ...ommend you close all your open files before initiating this test 3 If AC power fails the UPS warns you with an audible alarm To silence the alarm press the On Button When the battery starts to get low the audible alarm will return and beep faster 2 3 Off Button The Off Button has two steps to shutdown UPS 1 Pressing the Off Button when AC power is available causes the UPS into the sleep mode We re...

Страница 15: ...resent charge of the UPS s batteries is shown 2 7 Fault code The relevant value appears at the upper screen There are two kinds of fault modes can be displayed Err0 UPS Fault Err1 Warning of overload exceeding 120 2 8 Status Indication UPS Status Indication LINE indicator The indicator illuminates when the line input voltage is normal BY PASS indicator The indicator illuminates when the loads are ...

Страница 16: ...S is turned off the Start Up on Battery function can be used to power up your equipment Do not connect too much equipment to the UPS during the Start Up on Battery operation 1 Disconnect the input ac power cord from the rear panel of the UPS 2 Press the on off button on the front panel until the UPS beeps 3 After you have finished using the UPS press the on off button to turn off the UPS 2 11 Data...

Страница 17: ... environment away from heat emitting appliances such as a radiator or heater Do not install this product where excessive moisture is present 4 The location should provide adequate air flow around the UPS with one inch minimum clearance on all sides for proper ventilation 3 3 Determining How Much Equipment You Can Connect to Your UPS 1 Make a list of all equipment that requires protection 2 Each pi...

Страница 18: ...e On Off button for 3 seconds on the front panel 3 We recommend that you charge the battery for six 6 hours before first use of your UPS You may use the UPS immediately without charging the battery but the backup time may be less than the rating The UPS recharges the battery automatically whenever AC power is available 3 5 Connecting Your Equipment to the UPS 1 For all UPS models except the 2xxV v...

Страница 19: ...PS1000B PS1500B PS2200B PS3000 11 3 DO NOT PLUG LASER PRINTERS INTO THE UPS BECAUSE THEY TYPICALLY DRAW TOO MUCH POWER ...

Страница 20: ...ion you may unplug the power cord of the UPS or simply press the On Button on the front panel During this test observe that your equipment operates properly and without interruption If you leave your UPS on continuously it is a good idea to perform a Test at least once a month If you unplug the power cord all models will beep once every 4 seconds You can press the Test Button to silence the alarm ...

Страница 21: ... V VA W Capacity 100 110 120V PS1000B RM 50 60 220 230 240V 1000 700 100 110 120V PS1500B RM 50 60 220 230 240V 1500 1050 100 110 120V PS2200B RM 50 60 220 230 240V 2200 1540 100 110 120V PS3000B RM 50 60 220 230 240V 3000 2100 Input Output Voltage AC Line Voltage Version Lower Limit Upper Limit 1xxV Rated Voltage 25 Rated Voltage 25 2xxV Rated Voltage 25 Rated Voltage 25 Output voltage regulation...

Страница 22: ...tery approaches final discharge Beep every second Overload Continuous buzzer UPS faulty Continuous buzzer Battery and Charger Battery type Maintenance free sealed lead acid Recharge time 6 to 8 hours typical from total discharge The UPS may be used immediately after discharge but will provide shorter backup time Battery Specifications PS1000B PS1500B PS2200B PS3000B DC voltage 24V 36V 48V 48V Type...

Страница 23: ...0 x 215 26 8 29 3 Product Name Dimensions Weight Kg W L H mm Net Shipping PS1000B RM 428 x 550 x 84 33 5 35 7 PS1000B RM 428 x 550 x 84 33 5 35 7 PS2200B RM 428 x 615 x 84 43 2 46 3 PS3000B RM 428 x 615 x 84 43 2 46 3 4 3 Environmental Specifications Operating Storage and Shipment Temperature 0 40 C 32 104 F 20 60 C 4 140 F Humidity 0 95 non condensing 0 95 non condensing Altitude 3 000 m 10 000 f...

Страница 24: ...load and reset the circuit breaker UPS over load LED lit continuous audible alarm UPS is overloaded Remove the least critical devices from the load Low Replace Battery LED is lit Battery voltage is too low or the battery is dead Recharge the battery for more than 4 hours and reset the UPS If the LED is still lit replace battery Site Wiring Fault LED is on Site wiring problem Call an electrician to...

Страница 25: ...authorized personnel away from the batteries CAUTION Except for the battery the unit contains no user serviceable parts Repairs should be performed only by factory trained service personnel CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries 1 Remove watches rings or other metal objects 2 Use...

Страница 26: ...ons in section 6 1 before performing the following steps 1 Remove the two screws on the front panel 2 Pull and open the cover 3 Remove the screws of the battery retaining plate 4 Pull out the battery 5 Disconnect the two wires connecting the battery pack to the UPS 6 Connect the wires to the new battery pack making sure that the red wire is connected to the red battery terminal and the black wire ...

Страница 27: ...1 before performing the following steps 1 Remove the two screws on the front panel 2 Pull and open the cover 3 Remove the screws of the battery retaining plate 4 Pull out the battery 5 Disconnect the two wires connecting the battery pack to the UPS 6 Connect the wires to the new battery pack making sure that the red wire is connected to the red battery terminal and the black wire is connected to t...

Страница 28: ...ring the following procedure Please note that if you choose to leave the UPS on when the battery is removed it will not be able to power your equipment if a power failure occurs Please read the cautions in section 6 1 before performing the following steps 1 Remove the front panel 2 Remove the screws of the battery box 3 Pull out the battery box 4 Change and Slide the new battery box into the UPS 5...

Отзывы: