(1)Input power to low or no utility
Recover utility to /-20%
(2)Battery voltage decreases to low
voltage point
Unload to 10%~20% of load
(3)Ol-3320 detects circuit error
Replace ol-3320
(4)Ol-3302 detects circuit error
Replace ol-3302
(5)Ol-3300 feedbacks circuit error
Replace ol-3300
Battery is in low voltage
and UPS is about to be
shut down
(6)Error on ol-3300 program
parameter
Correct program parameter
(1)No battery
Add battery
(2)Battery power is not insufficient Recharge
battery
(3)Ol-3302 detects circuit error
Replace ol-3302
Error on battery test
(4)Ol-3300 program parameter
inaccuracy
Correct program parameter
(1)Emergency switch functions
Recover Emergency Switch
(2)Input short circuit
Eliminate short circuit
(3)Ol-3304 detects circuit error
Replace ol-3304
Emergency power
functions
(4)Ol-3300 detects circuit error
Replace ol-3300
Содержание DS-C33 100K
Страница 1: ......
Страница 7: ...Drawings 2 2C and 2 2D are the assembly diagrams of DS C33 series 45K 60K 80K Fig 2 2C ...
Страница 8: ...Fig 2 2D ...
Страница 9: ...Drawings 2 2E and 2 2F are the assembly diagrams of DS C33 series 22 5K 30K Fig 2 2E ...
Страница 10: ...Fig 2 2F ...
Страница 11: ...Drawings 2 2G and 2 2H are assembly diagrams of DS C33 series 10K 15K Fig 2 2G ...
Страница 12: ...Fig 2 2H ...
Страница 25: ...BATTERY TEST 30 Seconds 1 Month 3 Month Test OFF SUCCEED Waiting SUCCEED SUCCEED SUCCEED C 4 2 ...
Страница 28: ...TIME SET DATE 200 TIME F 1 Date Time Set Y M D 200 H M S Succeed ...
Страница 38: ...Fig 5 1 1 ...
Страница 40: ...Fig 5 3 ...