Table 4-2-1
When installing the UPS, please refer to table of 4-2-1 for corresponding input/output circuit breaker.
Refer to table 4-2-2 for wire specifications and capacity
Insulating Wire
Acceptable highest temperature of insulating
materials
1 PVC
wire
2 RB
wire
60
℃
3 Heatproof PVC wire
4 PE
Wire
75
℃
5 SBR
Wire
6 Artificial rubber wire
80
℃
7 EP rubber wire
8 Cross connect PE wire
90
℃
Ampere capacity for every kind wire(ambient temperature 35
℃
)
Copper
conducting wire
60
℃
insulation 75
℃
insulation
80
℃
insulation 90
℃
insulation
wire
SWG AWG
number
diameter
Ampere capacity (A)
2.0 14 7/0.6
20
3.5 12 7/0.8
30
5.5 10 7/1.0
40
8 8 7/1.2
55
65
70
80
14 6 7/1.6
80
95
100
110
22 4 7/2.0
100
125
135
145
30 7/2.3
125
150
160
170
38 2 7/2.6
145
180
190
205
50 19/1.8
175
210
220
245
60 0 19/2.0
200
240
250
280
80 19/2.3
230
285 300 330
100 19/2.6
270 330 350 380
125 19/2.9
310 380 400 440
150 37/2.3
360 440 460 505
200 37/2.6
425 520 550 600
250 61/2.3
505 615 650 710
325 61/2.6
590 720 760 830
400 61/2.9
680 825 870 995
Wiring
500
61/3.2 765
930
985
1080
Содержание DS-C33 100K
Страница 1: ......
Страница 7: ...Drawings 2 2C and 2 2D are the assembly diagrams of DS C33 series 45K 60K 80K Fig 2 2C ...
Страница 8: ...Fig 2 2D ...
Страница 9: ...Drawings 2 2E and 2 2F are the assembly diagrams of DS C33 series 22 5K 30K Fig 2 2E ...
Страница 10: ...Fig 2 2F ...
Страница 11: ...Drawings 2 2G and 2 2H are assembly diagrams of DS C33 series 10K 15K Fig 2 2G ...
Страница 12: ...Fig 2 2H ...
Страница 25: ...BATTERY TEST 30 Seconds 1 Month 3 Month Test OFF SUCCEED Waiting SUCCEED SUCCEED SUCCEED C 4 2 ...
Страница 28: ...TIME SET DATE 200 TIME F 1 Date Time Set Y M D 200 H M S Succeed ...
Страница 38: ...Fig 5 1 1 ...
Страница 40: ...Fig 5 3 ...