20
2.
Repeat steps as AC mains connection
3.
Fix them on AC Loads terminals
Connecting PV
1.
If there is DC switch on SP5000 Vitality Eco,
Switch off it in advance
2.
Use following connectors for PV DC cables
•
Wieland PST40i1 (Preferred)
•
Multi-Contact MC4
3.
Prepare wires according table below
4
Cross
Section
(mm
2
)
Maximum Length for 1% Loss
(Meter)
SP5000 Vitality Eco
1.5
4
2.5
6
4
10
6
23
4.
Plug connectors to SP5000 Vitality Eco
Disconnect PV
To disconnect PV cables, please
1.
Turn off DC switch if available in advance
2.
Push in the inter-locker on PV connectors
3.
Pull off the connectors & cables
Connecting Battery Bank(s)
The voltage of battery bank is 48V
DC
. The recommended numbers of battery
packs are 1~5. Please refer to specification for recommended battery type.
There will be some other batteries can be used, please contact your local
dealer and service for latest information.
4
The table is based on 20°C environment, installer need to adjust according to application and
local regulation