26
Control Your Generator
If your generator is equipped with remote start/control function, you can
connect a wire to “Generator Remote Control” to control it. It is a normally
open dry contact inside the terminal. Before end of discharging, those 2
terminals will be short; this can be used to enable a generator.
Once this contact is active, it will remain close until AC mains come back.
To connect this control, please
1.
Prepare a wire-cable
2.
Unplug the socket on “Remote Generator Control”
3.
Connect and secure cable terminals on this plug
4.
Insert this plug back
Only one AC power source can be connected
You can EITHER connect grid OR generator only. These 2
sources cannot be connected to SP Vitality-S in the same time.
Do not connect generator for on-grid operation
This could damage the generator by inverter feed-in.