EN-9
-LED ON/OFF
POSITION
FUNCTION
ON
(Factory default) The LED lights when someone is detected.
OFF
The LED does not light even if someone is detected.
MW range selector
MW sensitivity adjustment
Anti masking sensitibity
selector
DIP switch
1. LED ON/OFF
2. PIR IMMUNITY
3. AUX INPUT
4. TROUBLE OUTPUT
5. MICROWAVE IMMUNITY
6. (Reserved)
Do not touch
PIR sensitivity
selector
Do not touch
Notes>>
• The alarm does not output unless both the main unit and the satellite detect someone within 60 sec.
• If the OR mode is selected without a satellite unit connected, the alarm is generated continuously.
Notes>>
Use this when not wiring a detected trouble input terminal on the control panel.
By connecting a satellite unit (another warning sensor), you can extend the detection area and correct false alarms.
As a satellite unit, you can use any general no-voltage contact output (NC) warning sensor, including the following.
<Infrared (AIR) sensors, thermal line (PIR) sensors, universal magnet switches, etc.>
AND
(Factory default)
OR
When both the main unit and the satellite detect someone,
the alarm is output. Set to this when not connecting a
satellite unit.
When either the main unit or the satellite detects someone,
the alarm is output.
ON
(Factory default)
OFF
Anti-masking signal is output from TROUBLE OUTPUT
terminal.
Anti-masking signal is output from both TROUBLE and
ALARM OUTPUT terminal.
4
SETTING
4-1
FUNCTION
DIP switch 1
-PIR IMMUNITY
POSITION
FUNCTION
STD
(Factory default)
PIR IMMUNITY logic is not activated.
IMMUNITY
PIR IMMUNITY logic is activated.
Use this under harsh environment (e.g. small animal).
DIP switch 2
-AUX INPUT
POSITION
FUNCTION
DIP switch 3
Trouble output is used for anti-masking signal. When an object is placed close to the lens surface, for a period of
more than 180 sec., the IR Anti-Masking circuit is activated and generates a trouble signal.
-TROUBLE OUTPUT
POSITION
FUNCTION
DIP switch 4
HX-40
HX-40AM
HX-40DAM
HX-40
HX-40AM
HX-40DAM
HX-40
HX-40AM
HX-40DAM
HX-40
HX-40AM
HX-40DAM
ON
OFF
IMMUNITY
STD
OR
AND
ON
OFF
PIR AREA SETTING
DETECTION AREA
(SIDE VIEW)
MW RANGE
SELECTOR
MW SENSITIVITY
ADJUSTMENT
Factory default
0
MW
PIR
MID
M
H
L
1
0
MW
PIR
HIGH
M
H
L
1
2
0
MW
PIR
MID
M
H
L
1
3
2
0
MW
PIR
LOW
M
H
L
12 m
(40 ft.)
9.0 m
(30 ft.)
5.5 m
(18 ft.)
4.0 m
(13 ft.)
SHORT
SHORT
SHORT
HIGH
MIDDLE
LOW
HIGH
STD
OFF
HIGH
MIDDLE
(Factory default)
LOW
High sensitivity
Middle sensitivity
Low sensitivity
Caution>>
When closing the cover, do not leave any object within 1.0 m (3.3 ft.) from the unit.
-MICROWAVE IMMUNITY
POSITION
FUNCTION
STD
(Factory default)
MICRO WAVE IMMUNITY logic is not activated.
IMMUNITY
MICRO WAVE IMMUNITY logic is activated. Use this under
harsh environment (e.g. vegetation sway).
DIP switch 5
HX-40
HX-40AM
HX-40DAM
-PIR SENSITIVITY
POSITION
FUNCTION
HX-40
HX-40AM
HX-40DAM
-MW RANGE SELECTOR/MW SENSITIVITY ADJUSTMENT
HX-40
HX-40AM
HX-40DAM
RANGE SELECTOR/
SENSITIVITY
ADJUSTMENT
PIR SENSITIVITY SELECTOR
HIGH
STD
(Factory default)
OFF
High sensitivity
Standard sensitivity
Disabled
-ANTI-MASKING SENSITIVITY
POSITION
FUNCTION
HX-40
HX-40AM
HX-40DAM
ANTI-MASKING SENSITIVITY SELECTOR
IMMUNITY
STD
LONG