36
Setting detection area
< Before Position Setting >
Sensor Direction
Select the direction of the sensor.
Select whether the installation is for detection from the non-secured side to the secured side or from the
secured side to the non-secured side.
Mounting
height
Set the values of Mounting height [2,300 to 2,900] mm.
Setting detection area
Top left position
Select the click the top left position shown on the floor on the screen as shown in the figure above (on the
picture I wrote an appropriate detection zone). This position can be fine-adjusted by using the arrow buttons
on the screen.
Bottom right position
Select the click the bottom right position shown on the floor on the screen as shown in the figure above.
This position can be fine-adjusted by using the arrow buttons on the screen.
< After Position Setting >
<Note>
Set the detection area to cover all floor in the interlock area except a part of wall and equipment on the
wall, for example Biometric reader.
Those obstacles may cause false rejections.