Fire Protection  |  Data sheet No. 43104  | Version 02-2016  | 

1

 | 

8

Control unit STG 1.2  

for DRM ceiling smoke detector / DKM manual call point – bus compatible

Technical data

Supply voltage:

 

24 V AC + / -10%

 

24 V DC +15% / -10%

Power consumption:

 

250 mA (normal operation)

 I

max

 2.5 A (alarm – 20 detectors)

 I

max

 6.2 A (0.02 s short circuit)

Relay outputs:
Alarm:

 

1 changeover contact

 

240 V AC / 30 V DC, 8 A

 

1 NC

 

240 V AC / 30 V DC, 8 A

Contamination:

 

1 changeover contact

 

400 V AC / 300 V DC, 6 A

Failure:

 

1 changeover contact

 

400 V AC / 300 V DC, 6 A

Service:

 

1 changeover contact 

(service mode) 

400 V AC / 300 V DC, 6 A

Notifications:
Display:

 

Plain text display status

 

DRM / DKM, configuration

Alarm:

 

red LED

Contamination:

 

yellow LED

Failure: 

 

yellow LED

Operation:

 

green LED

Housing:

 

plastic ABS

Dimensions (W x H x D):

  160 x 85 x 50 mm

Installation:

 

DIN-rail, panel

Protection class:

 IP20

Ambient temperature:

 

0 °C to 50 °C

Connection:

 

spring terminals 0.5 – 2.5 mm²

• 

Can connect up to 99 DRM 3.3 or DRM 3.3-N 

ceiling smoke detectors / DKM 3.3 manual call 

points

• 

Possible to query each detector as to status 

and contamination

• 

Large LCD display and 4 additional LEDs

• 

RS485 Mod-Bus interface for informal  

transmissions to the building management 

system (BMS)

• 

4 changeover contacts for alarm, failure,  

service and contamination

• 

1 NC for alarm

• 

Monitoring for short circuits and cable breaks

Function

Up to 99 type DRM 3.3  or DRM 3.3-N/ DKM 3.3 ceiling smoke 
detector or manual call points can be monitored by the STG con-
trol unit. The STG communicates with its connected detectors 

by way of their security monitored system ring buses. Smoke 
alarms, failure and contamination messages are all forwarded 
from the detectors to the STG and shown on a display. This 
makes it possible for a technician or custodian to supervise all 
the connected detectors at a glance. The STG has one changeo-
ver relay each for alarm, contamination, failure and service mode 
signalling. With the alarm message there is a relay available 
which serves as an NC contact. With this relay the messages can 
be reported to a central building management system (BMS). 
The STG 1.2 additionally has an RS-485 interface to the BMS, 
which also exports all of this data including the status of indivi-
dual detectors via a Modbus RTU protocol. With this interface it 
is also possible to evaluate the STG via PLC control or a PC.

Important note: 

In addition, please note the separate 

DRM / DKM data sheets.
If an alarm occurs at one or more connected detectors, the red 
LED lights up on the STG, a message is issued to the STG display, 
and the corresponding NC contact and changeover contact at 
the STG drop out. By pressing the reset button the relay contact 
can be restored, but the corresponding alarm must be termina-
ted/disabled first. In case of failure, connection problems as well 
as contamination of one or more of the detectors, the yellow 
contamination LED on the STG lights up and the corresponding 
changeover relay of the STG drops out. If no connection to a 
duct smoke detector can be made, a failure message appears 
on the STG. If a new detector is connected in the service mode, 
a corresponding message appears on the display. If the STG is 
in service mode the service relay drops out. Failure and alarm 
messages of the connected detectors must be acknowledged 
once more through the STG “alarm /reset” button.

Содержание STG 1.2

Страница 1: ...em ring buses Smoke alarms failure and contamination messages are all forwarded from the detectors to the STG and shown on a display This makes it possible for a technician or custodian to supervise a...

Страница 2: ...ervice mode Note The service mode is used to integrate a new detector or for system maintenance Operating mode The operating mode is accessed by storing the selected configuration All connected detect...

Страница 3: ...rding to electrotechnical regulations Please ensure to connect the current ceiling smoke detector model The older version type DRM 3 3 has been replaced by version DRM 3 3 N Contact depictions are wit...

Страница 4: ...ld be installed in a separate conductive and grounded cable trunking It is important to ensure that no potential differences between devices can occur on the Modbus perform equipoten tial bonding The...

Страница 5: ...reafter the data register follows The register set is dependent on the query and can vary between 1 and 125 Register description Each register consists of 2 bytes With Modbus RTU it is possible to sen...

Страница 6: ...lure LED lights up 0 Failure LED does not light up Bit 12 1 Operation LED lights up 0 Operation LED does not light up Bit 11 1 Alarm relay energized 0 Alarm relay de energized Bit 10 1 Failure relay e...

Страница 7: ...ctor has an internal error 0 No internal error Bit 3 1 Malfunction Detector no longer recognized in the bus 0 No malfunction Bit 2 1 Alarm 0 No alarm Bit 1 0 0 No detector connected at this address 1...

Страница 8: ...yte 3 Byte 4 Byte 5 STG address Function Error code CRC LSB CRC MSB Byte 0 Address of the STG 1 2 Byte 1 Function byte Here the function byte for the query is sent back However the MSB is set by the f...