Volume flow indicator / monitor / transmitter SENSO-X® VPX

4

 | 

6

  |  Sensors PG1  |  Data sheet No. 13170  |  Version 03-2020

The sliding switch S5 is for inserting a 120 ohm terminal resistor. 
Ex factory the switch is in off-position (OFF pos. = left).

Default (factory) Modbus  settings 
Baud rate:  

9600 

data bits:  

start bits:  

stop bits:  

Modbus address:   1
parity:  

even

The following Modbus parameter options are available via the menu or the NFC tool configuration program:
bus adresse:  

1-127

baud rate:  

9.6k, 14.4k, 19.2k, 56k

parity:   

even (1 startbit, 8 datenbits, 1 stopbit),  

 

odd (1 startbit, 8 datenbits, 1 stopbit),  

 

none (1 startbit, 8 datenbits, 2 stopbits) 

Implemented Modbus function: Read Holding Registers function 0x03

Register PWM 

address

Name

File type

Raw data

Description

0 (0x00)

40001

pressure

unsigned 16

0 to 1,000 or 4,000

measured differential pressure in Pa

1 (0x01)

40002

limit (low word)

unsigned 32

0 to 65,535

Set limit value in selected unit  

of measure, see register 7, e.g.  

0 to 99,999 m³/h

2 (0x02)

40002

limit (high word)

0 or 1

3 (0x03)

40004

output analog

unsigned 16

0 or 1

0 = 0 – 20 mA or 0 – 10 V 

1 = 4 – 20 mA or 2 – 10 V

4 (0x04)

40005

unassigned

5 (0x05)

40006

flow  (low word)

unsigned 32

0 to 65,535

calculated volume flow in m³/h  

0 to 99,999

6 (0x06)

40007

flow (high Word)

0 or 1

Modbus connection diagram:

Note:

  

Floating switch contacts “CO, “NC” and “NO” may only be used for 230 V AC or  
24 C AC/DC .
Disconnection or electrical protection equipment must be  provided by the 
customer. The 24V AC/DC supply voltage requires a local fuse for max. 6 A or  
a supply unit with a power output limit of 6 A.  

Caution:

All cable installation and connection work must be left to a duly qualified elec-
trician. Make sure that all cables are connected in accordance with the relevant 
electrical regulations. The cable sheath must reach as close as possible to the 
terminals. Braided wires longer than 10 mm must be secured near the terminal 
with a cable clip or similar or must be insulated in pairs using, e.g., suitable shrink 
tubing (see installation example). 

Installation example

:

Terminal J1 only present in bus version. 
For electrical connections see previous page.

Modbus RTU

Overview of registers