Volume flow indicator / monitor / transmitter SENSO-X® VPX

2

 | 

6

  |  Sensors PG1  |  Data sheet No. 13170  |  Version 03-2020

Built-in version

Mill a 115 mm Ø hole in the sandwich plate or cabinet door 
and push the functional part through the opening from the 
front. The mounting direction is indicated by an arrow pointing 
upward on the back of the device. Screw the threaded rod 
into the threaded sleeve with a screwdriver; slip the mounting 
bracket over it and secure with a wing nut. When connecting 
the pressure transfer hoses, care must be taken to comply with 
the direction of the pressure (+/-). Finally, the front panel can be 
snapped into place. 

Surface-mounted housing

Screw the functional part onto a wall, duct or similar and then 
connect it to the power and pneumatic lines. Then slip the ring 
cover over the functional part and snap on the front cover. 

Design

The 

built-in version

 of the 

SENSO-X

®VPX consists of a round 

section and a square or round front cover. The instrument is 
optimized for installation in ventilation devices and control 
cabinets. The two pressure test points, (positive 
pressure side) and - (negative pressure side), are sunk into the 
housing on the back. In the middle is a threaded sleeve. Attach 
the retaining bracket using the supplied threaded rod and wing 
nut. The wing nut is secured against loosening. Two cable  
breakthroughs are provided on the back of the housing. Two 
M16 x 1.5 screw joints are included in the assembly kit. An 
integrated O-ring serves to seal the functional part against the 
mounting surface. The arrow on the back of the device points 
upward in the correct mounting position.  

The 

surface-mounted version

 of the 

SENSO-X® 

VPX consists of 

a round functional part with three screw-on mounting brackets, 
a ring cover and a snap-on front cover. The two measurement 
connections, (positive-pressure side) and – (negative-
pressure side), exit at the bottom. Exiting at the bottom are also 
two strain relief elements. 

Built into the functional part in all versions, and visible from the 
front, are an LCD display, an LED to indicate when limit values 
are exceeded and 4 function keys.
After installation and configuration of the device, the front 
cover is snapped onto the functional part. Due to 3 guided  
notches this is only possible in the correct position. Removing 
the front cover is done by pulling with both hands or by using  
a screwdriver.

Operating principle

The measured differential pressure is transmitted via flexible 
hoses and connecting nipples onto the piezoelectric differential 
pressure sensor, electronically evaluated, converted into units of 
volume flow taking into account the programmed k-factor and 
density ρ and displayed on the LCD indicator.

This calculation is based on the following formula 

Vh  = volume flow [m³/h] 

K = K-factor [m²s/h] 

∆p = differential pressure [Pa] 

ρ = air density [kg/m³]

V

h

 = K  x

2 x ∆p

ρ

Note: Many fan manufacturers use simplified basic formulas 
and accordingly modified K-values. State the manufacturer 
when entering the K-factor, and the transmitter will take 
this into account. Please refer to the table below for identi-
fiers of the most common manufacturers:

Non-binding information. Please note the current
data sheets of the manufacturers. Subject to change. If the 
manufacturer of your choice is not listed, enter the K-factor 
manually. Use the setting D = “Uni” for this purpose. This is also 
the default setting.
The additional parameter “No. of fans” allows for fan walls/fan 
grids. Enter the number of fans. The default setting is 1.

Activation and operation

Make all electrical connections before connecting the supply 
voltage. Connect the 24 V supply voltage with the correct polarity 
to start up the 

SENSO-X®

 VPX. 

The device is ready for use immediately.
To set the parameters either take off the front panel and enter 
the desired settings via the 3 keys or use the NFC tool (Windows 
program for PCs: see Specification Sheet 13180; or Android App 
for smartphones / tablets in the Google Play Store).

Setting display unit (dimension)

A brief push of the lower key (S1) in normal operation mode swit-

Manufacturer

Manufacturer 

identifier 

„Manufactor“

Example 

types

Calculated  

K-factor K1  

transmitter

ebm-pabst

A

R3G, K3K, … K = 0,7746 * K

ebm

Fläkt

B

CXLF, GXLB, 

GPEB, …

K = 2788,5 / K

Fläkt

Nicotra  

Gebhardt

C

RZR, RZA, … K = K

Gebhardt

Rosenberg

C

DKH, GKH, … K = K

Rosenberg

Ziehl-Abegg

A

ER…C, 

GR…C, …

K = 0,7746 * K

Ziehl

Comefri

C

-

K = K

Comefri

Unassigned  

value / uni-

versal

D

-

K =  

(enter value)