Volume flow indicator / monitor / transmitter
SENSO-X®
VPX
Sensors PG1 | Data sheet No. 13170 | Version 03-2020 |
1
|
6
•
Large LCD display
•
Volume flow up to 99,999 displayed in
numerals or as an indicator bar in any of the
following units: m³/h, l/s, ft³/min
•
Limit displayed up to max. volume flow
•
Working range displayed (Range max)
•
Three-color LED: red for limit value undershoot,
yellow for fault and green for overshoot
•
Temperature / Absolute pressure transducer
•
NFC parametrisation of limit, range max,
signal range for analog output, K-factor and
air density ρ
•
Optional Modbus output
•
Power supply: 24 V AC at 50 / 60 Hz or 24 V DC
•
Available in two built-in and one surface-
mounted versions
Technical data
Housing:
high impact ABS
Front panel color:
antique white
Lower housing color:
anthracite
Protection class:
surface-mounted type (AP) IP 65
built-in type IP 54 /
built-in type with additional sealing
(accessory) IP64
Operating temperature:
-20 °C to 65 °C
Storage temperature:
-20 °C to 70 °C
Relative humidity:
max.
95 % non-condensing
Front cover dimensions
- square:
182 x 140 x 21 mm [L x W x H]
- round:
143 mm Ø
Dimensions of
surface-mounted type:
165 x 71 mm [Ø x T]
Hose connection:
2x 6 mm Ø
Working and
measuring ranges:
see table
Working range:
adjustable via keys and NFC tool
Burst pressure:
20 kPa (VPX1000)
40 kPa (VPX4000)
Protection class:
II (IEC 60536)
Error margin:
+/- 1 % of measuring range
(@ -5 to 65 °C)
Power consumption:
24 V DC 41 mA
24 V AC 81 mA
Long-term stability:
≤ ± 0.5 % FS/a
Supply voltage:
13.5 – 36 V DC or
13.5 – 30 V AC at 50/60 Hz
Output analog:
linear 0 – 10 V (max. 0.1 mA) or
4 – 20 mA (max. load 600 Ω).
Output digital:
relay (250 V AC 6 A, 30 V DC 5 A),
changeover switch, closed-circuit
principle, freely selectable limit value.
Modbus optional.
Cable gland:
M16
Cable connection:
Spring terminals 0.2 – 1.5 mm²
Installation
All work (such as installation, electrical connection, startup, ope-
ration, and maintenance) must only be performed by sufficiently
qualified tradesmen. The respectively applicable local rules and
regulations (e.g. national building codes, electrical/VDE regula-
tions, etc.) must be observed. Installers and operating entities
are required to sufficiently familiarize themselves before startup.
Read the product description before operating the equipment.
Verify that the product can be used for the relevant application
without restrictions. We are not liable for printing errors and
changes after printing. Appropriate use implies compliance with
operating and installation instructions. We are not liable for losses
due to inappropriate use. Unauthorized or inappropriate mani-
pulations or modifications of the device render the operating
permit, the product warranty and warranty claims null and void.
Types
Type
Type
Measuring
Measuring
range
range
Working range
Working range
(output signal)
(output signal)
Units of
Units of
measure /
measure /
output*
output*
Limit value
Limit value
monitoring
monitoring
VPX1000
0 – 1,000 Pa
0 – 99,999 m³/h
freely adjustable in
1 m³/h-increments
m³/h, l/s,
ft³/min
Freely selectable.
LED/bar -ind
switching output for
undershoot
VPX4000
0 – 4,000 Pa
0 – 99,999 m³/h
freely adjustable in
1 m³/h-increments
m³/h, l/s,
ft³/min
Freely selectable.
LED/bar -ind
switching output for
undershoot
* analog output 0 – 10 V or 4 – 20 mA linear depending on selected working range and unit of
measure.