background image

  

Fire Protection  |  Data sheet No. 40102  |  Version 01-2011  | 

3

 | 

4

Ceiling smoke alarm DRM 3.3 

Electrical connection on STG 1.2 control unit

All work on electrical installations or equipment must only be performed in accordance with electrical engineering principles by a 
trained electrician or by an instructed person under the direction and supervision of a trained electrician.

Contamination

Service

Malfunction

Alarm

GLT bus 

A

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

B

A

B

GND 485

GND smoke alarm

Smoke alarm bus

Modbus 

RTU to 

the BMS

Shield

Power supply for STG

Manual call point DKM 3.3

Ceiling smoke detector 

DRM 3.3

Loop 

+

 IN

Loop 

+

GND

in

in

in

in

out

out

out

out

GND

Loop 

+

Loop 

Loop 

Loop 

 IN

Loop 

+

 OUT

Loop 

 OUT

Scr

een IN

Scr

een OUT

24 V AC/DC

24 V AC/DC

Shield

1

2

5

7

6

1

2

5

7

6

Contacts are shown disconnected from power (alarm)

Alarms are supplied with power from the system ringbus. The bus cable must be shielded on both sides (terminal 7).

The maximum bus length is 250 m (loop length 500 m).

Smoke alarm address

Each connected alarm must be assigned a dedicated, unique BUS address between 1 and 99. This is accomplished with the PG 3.3 
programming tool (accessory) The standard default address is 127 and is therefore not recognized by the STG. On request, Opper-
mann can configure the alarms with custom BUS addresses (indicate in your order - particularly important when ordering replace-
ment parts). A fault alarm is triggered if the same alarm address is assigned twice on the ringbus. If the alarm message is changed, 
the alarm must be reregistered with the STG in service mode. The positioning of addressed DKMs in the ringbus is arbitrary.

Отзывы: