onset
®
POWER MONITORING
INSTALLATION GUIDE
14724-D
PAGE 2
© 2011–2013 Veris Industries and Onset Computer Corporation
Veris and the Veris “V” logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Onset, HOBO, HOBOware, and HOBOlink are trademarks or registered trademarks of Onset Computer Corporation.
DIMENSIONS
Housing
Bottom View (DIN Mount Configuration)
Bottom View (Screw Mount Configuration)
OPERATION
The E50B2 DIN Rail Power Meter provides a solution for measuring
energy data with a single device. Inputs include Control Power, CT,
and 3-phase voltage. The LCD screen on the faceplate allows instant
output viewing.
The meter is housed in a plastic enclosure suitable for installation on
T35 DIN rail according to EN50022. The E50 can be mounted with
any orientation over the entire ambient temperature range, either
on a DIN rail or in a panel. The meter is not sensitive to CT
orientation to reduce installation errors.
DATA OUTPUTS
Native:
•
Volt Ampere Reactive Hour (VARh)
•
Watt Hours (Wh)
•
Ampere Hour (Ah)
Derived in HOBOware®:
Derived Channel
Unit
Calculation
Reactive Power
VAR
VARh/h
Volt-Amps
VA
SQRT(Wh^2 + VARh^2)/h
Volts
V
SQRT(Wh^2 + VARh^2)/Ah
Power Factor
PF
Wh/SQRT(Wh^2 + VARh^2)
True Power
W
Wh/h
True Power
KW
W/1000
Kilowatt Hours
KWh
Wh/1000
Amp A
Ah/h
(where ‘h’ is hours = Logging Interval/3600)
PRODUCT DIAGRAM
www.
.com
1.800.561.8187