8
Type
Air output
[m3/h]
Heating output
[kW]
Temperature at exhaust
[°C]
Pressure loss
[kPa]
VCE-B-100-V-...
1300
9,6
42,3
0,5
VCE-B-150-V-...
1900
15,7
44,9
2,6
VCE-B-200-V-...
2550
22,4
46,6
3,2
Air curtain with a water heat exchanger for a water temperature gradient of
90/70
°C
and a suction air temperature of +18 °C.
Type
Air output
[m3/h]
Heating output
[kW]
Temperature at exhaust
[°C]
Pressure loss
[kPa]
VCE-B-100-V-...
1300
8,0
37,9
0,4
VCE-B-150-V-...
1900
13,0
40,0
2,0
VCE-B-200-V-...
2550
18,6
41,4
2,2
Air curtain with a water heat exchanger for a water temperature gradient of
80/60
°C
and a suction air temperature of +18 °C.
5. TECHNICAL PARAMETERS
6. INSTALLATION
6.1 OPERATING CONDITIONS:
The air curtain is designed to be operated in a dry indoor en-
vironment at an ambient temperature in the range from 5°C
to +40°C and at a relative humidity of up to 80%, for transpor-
ting air that is free of dust, fats, chemical emissions and other
pollutants. The electrical protection rating of the air curtain is
IP 20 (protection against bodies larger than 12.5 mm, not pro-
tected against water). Air curtains with an electric heater are
fitted with an operating thermostat with an automatic reset
(located on every heating element) and an emergency ther-
mostat with a manual reset. The hot water heat exchangers
are intended for a maximum operating water temperature of
+100°C and a maximum operating pressure of 1.6 MPa. The
air curtain design must always be drawn up by a HVAC and
central heating project engineer.
6.2 INSTALLATION CONDITIONS:
The installation and assembly of an air curtain may only be
carried out by a person with relevant qualifications, that has
suitable tools and equipment at their disposal. The air curtain
is supplied with 2x mounting brackets bolted to the top part
of the curtain‘s case as standard. If you wish to install the cur-
tain on threaded rods, it is necessary to order this separately.
For the correct function of the curtain, you should adhere to
the following rules:
Type
Air output
[m3/h]
Heating output
[kW]
Temperature at exhaust
[°C]
Pressure loss
[kPa]
VCE-B-100-V-...
1300
6,3
33,6
0,2
VCE-B-150-V-...
1900
10,3
35,2
1,5
VCE-B-200-V-...
2550
14,8
36,4
1,4
Air curtain with a water heat exchanger for a water temperature gradient of
70/50
°C
and a suction air temperature of +18 °C.
Type
Air output
[m3/h]
Heating output
[kW]
Temperature at exhaust
[°C]
Pressure loss
[kPa]
VCE-B-100-V-...
1300
4,7
29,5
0,2
VCE-B-150-V-...
1900
7,7
30,7
1,0
VCE-B-200-V-...
2550
12,2
31,5
0,8
Air curtain with a water heat exchanger for a water temperature gradient of
60/40
°C
and a suction air temperature of +18 °C .
The warm water heat exchanger made from Cu/Al materials is intended for a max. operating water
temperature of +100 °C and a max. operating pressure of 1.6 MPa.
Содержание ESSENSSE
Страница 2: ......
Страница 3: ...3 EN INSTRUCTION MANUAL AIR CURTAIN ...
Страница 15: ...15 ...
Страница 16: ...16 ...
Страница 17: ...17 SM MODULE INSTALLATION OPERATION AND HANDLING ...
Страница 23: ...23 ...
Страница 24: ...24 ...
Страница 25: ...25 FI KÄYTTÖOHJE ...
Страница 37: ...37 ...
Страница 38: ...38 ...
Страница 39: ...39 SM MODUULI KÄYTTÖOHJE ...
Страница 45: ...45 ...
Страница 46: ...46 ...
Страница 47: ...47 SWE BRUKSANVISNING LUFTRIDÅN ...
Страница 58: ...58 ...
Страница 59: ...59 SM STYRMODULER INSTALLATION DRIFT OCH HANTERING ...
Страница 65: ......
Страница 66: ...onnline ...