User guide Automatic Transfer Switch

User guide Automatic Transfer Switch 

 Page 11

7    Communication Port

The ATS is supplied with the following communication ports:

•    Serial port is available with RS232 com. port and USB com. port on the front panel.

 

PLEASE NOTE 

the use of one port automatically excludes the other.

•    Contacts port on the rear panel. 

Serial Ports: RS-232 & USB connectors

Put the input power switch in “ON” position. The output will then be supplied by the source set as selected.

PIN#

Name

Type

Signal

1
2

TX

OUT

Serial line TX

3

RX

IN

Serial line RX

4
5

GND

POWER

6

+12V

POWER

7
8
9

PIN#

Signal

1

VBUS

2

D-

3

D+

4

GND

RS-232 connector

USB connector

PLEASE NOTE

The utilization of the communication port is optional and it is not necessary for the correct  
functioning of the ATS.

Contact Ports

The contacts port is formed using six (6) pins numbered from left to right (see fig. 1), which can be connected 
to an external monitoring system (such as a BMS) in order to monitor the operational status of the ATS.
The external equipment must respect the voltage and current characteristics of contacts port.

Focus on contacts port

The contacts port provides the following pins:

•  Pin 1:   common contact.

•   Pin 2:   “Source B” active contact  

(if the contact between “pin 1” and “pin 2” is closed, output is supplied by “Source B”).

•   Pin 3:   “Source A” active contact  

(if the contact between “pin 3” and “pin 1” is closed, output is supplied by “Source A”).

•   Pin 4:   “Source A” status OK contact  

(if the contact between “pin 4” and “pin 1” is closed, “Source A” is present and regular).

•   Pin 5:   “Source B” status OK contact  

(if the contact between “pin 5” and “pin 1” is closed, “Source B” is present and regular).

•   Pin 6:   Status OK contact  

(if the contact between “pin 6” and “pin 1” is closed, ATS functioning status is regular).

The following diagram shows the functioning of the contacts port.

Contacts port basic diagram

ATTENTION

The pins of the contact port are able to carry maximum current of 8A and maximum voltage of 250Vac.

Содержание ATS-16A

Страница 1: ...www online ups com USER MANUAL AUTOMATIC TRANSFER SWITCH Model ATS 16A ...

Страница 2: ... Introduction 4 2 Product Overview 5 3 Safety Warnings 6 4 Operation Indicators Status 7 5 Installation 8 6 Operation 9 7 Communication Port 10 8 Trouble Shooting 12 9 Specifications 13 10 Appendix 14 Imprint 15 ...

Страница 3: ... the ATS can also switch power back to the primary input when power to the primary input is restored Package contents ATS module User manual Mounting brackets Download from www online ups com 2 Product Overview Front View 1 Power switch for input source A 2 Power switch for input source B 3 Circuit breaker for output 1 4 Circuit breaker for output 2 5 USB communication port 6 RS 232 communication ...

Страница 4: ...PLEASE NOTE These instructions may be modified by the wiring regulations in force in the country where the ATS is purchased 4 Operation Indicators Status 1 Source preference selector 2 Priority setting LEDs 3 Power source status LEDs 4 Output source LEDs 5 Fault indicator 6 Alarm mute button Indication type LED description LED status Condition Alarm Priority setting LEDs Source A 2 ON Source A is ...

Страница 5: ...the ATS plug input source A connector and input source B connector to the two independent power sources or UPSs depending using the SCHUCKO IEC or IEC IEC 16A cables supplied Plug the user load to the output 10A Output 1 and 2 or 16A Output 3 sockets depending on user s requirements 6 Operation Power On Off Put the input power switch in ON position The output will then be supplied by the source se...

Страница 6: ...ee fig 1 which can be connected to an external monitoring system such as a BMS in order to monitor the operational status of the ATS The external equipment must respect the voltage and current characteristics of contacts port Focus on contacts port The contacts port provides the following pins Pin 1 common contact Pin 2 Source B active contact if the contact between pin 1 and pin 2 is closed outpu...

Страница 7: ...d to the load Therefore prior to attempting a reset of the thermal protection please check the connected loads rating and or determine if there are any problems Then once reset reconnect each load one at a time to ensure no problems exists The display shows nothing or provides incorrect information There is power supply problem in display Shut down the ATS completely and wait for a few seconds Swi...

Страница 8: ...k to Source B Setting Source B as priority power source and Source A is powering Low point 190V High point 248V Acceptable input frequency for Source A Source A will be power source during this range When input frequency of source A is beyond this range ATS will automatically switch to power from Source B 45Hz 55Hz Acceptable input frequency for Source B Source B will be power source during this r...

Страница 9: ...ONLINE USV Systeme AG Luise Ullrich Straße 8 DE 82031 Grünwald www online ups com ...

Отзывы: