V1.1-ENG
11
www.onlab.com.tr
MANUFACTURER SETTINGS
Constructional settings of the door mechanism used with Ondrive are encrypted under
“Manufacturer Settings” section for disabling users to reach those parameters. After the
parameter 29 in menu, when “Manufacturer Settings” is displayed on screen, press the ENTER
button and a 4-digit password will be asked by Ondrive. By entering the password, following
parameters will be displayed. Those parameters can be visualized until the power of the device
is OFF and ON again. Default password for manufacturing settings is “1 2 3 4”. Every
manufacturer can assign a new password using parameter 51, but this password cannot be
cancelled. If this password is entered as false for 5 times, a 6-digit PUK code will be needed.
This PUK code is generated from the serial number of Ondrive board. Manufacturer and user
PUK codes are different from each other.
Program
Factory
Settings*
Parameters / Explanations
40: LearningSpeed
6 cm/s
2-19 (Learning speed level)
41: Motion Direc.
NOT
INVERTED
NOT INVERTED / INVERTED (In door learning process, if the
door goes to closing direction firstly, change this parameter to
INVERTED.
42: OpenHoldForce
% 100
1-100(Open hold force setting. % of motor nominal current)
43: Cls.HoldForce
% 100
1-100 (Close hold force setting. % of motor nominal current)
44: SkateOpenSpe.
7 cm/s
1-20 (Speed level while opening the skate)
45: SkateCloseSpe.
7 cm/s
1-20 (Speed level while closing the skate)
46: Skate Distan.
6 cm
1-199 (Skate length)
47: Wheel Circum.
80 mm
30-999 (Circuimference of the wheel on the motor shaft)
48: Spd.Cnt.Level
16
1-20
Speed control sensitivity of the motor
(Increasing this parameter decreases the error and oscillations in
speed, but increasing this parameter more than required will result to
noise and vibrations on the motor)
49: Cur.Cnt.Level
4
1-20
Current control sensitivity of the motor
(Decreasing this parameter will decrease the response time to torque
change requirements but noise and vibration of the motor will
increase)
50: Reset Counter
(Toplam Çalışma Sayacını Sıfırlama)
51: SetMan.Passw.
(Used for changing manufacturer password.)
52: LearnPressLev
% 100
20-100(Pressure level at learning operation)
53: Op.Limit Dist
15 mm
5-50
54: Cl.Limit Dist
10 mm
1-10
55: PressDet.Time
1000 ms
20-2000
56: Standard Type
EN 81-20
EN_81_1_2_A3_1, EN_81_1_2_A3_2, EN_81_20
(There are 3 modes that are given above. At door closed position,
those modes will lead to different results in operation if there is no
OPEN and CLOSE signal.
EN_81_1_2_A3_1: Motor is deenergized.
EN_81_1_2_A3_2: Close hold force is applied to the motor.
EN_81_20: Door is opened until the skate is opened completely and
it will be stopped. Then, motor is deenergized.
99. Factory Set ?
(If this parameter is set, all of the parameter values will be reset to
factory settings.)
*Factory Setting values can be different in customer specific software.