CE-IO1600 User Manual
Coil Control 4
Write coil
Command 1
0x0004
The 4th DO
Coil Control 5
0x0005
The 5th DO
Coil Control 6
0x0006
The 6th DO
Coil Control 7
0x0007
The 7th DO
Coil Control 8
0x0008
The 8th DO
Coil Control 9
0x0009
The 9th DO
Coil Control 10
0x0010
The 10th DO
Coil Control 11
0x0011
The 11th DO
Coil Control 12
0x0012
The 12th DO
Coil Control 13
0x0013
The 13th DO
Coil Control 14
0x0014
The 14th DO
Coil Control 15
0x0015
The 15th DO
Coil Control 16
0x0016
The 16th DO
(
1
)
The Modbus device command supports the following Modbus addresses:
00001 to 09999 are discrete outputs (coils)
10001 to 19999 are discrete inputs (contacts)
30001 to 39999 are input registers (usually analog inputs)
40001 to 49999 are holding registers (usually store device configuration information)
In 5-bit code format, the first character determines register type, and the remaining 4 characters
represent address.
Address 1 starts from 0, such as 00001 corresponds to 0000.
(
2
)
Baud rate value corresponding table
(
3
)
The relay status can be queried through 30002 address or through 00001-00002 address,
but the control can only use 00001-00002 address.
30002 address data length is 16bit. Up to 16 relays can be represented.
The responding results as follow:
Bite
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Relay
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
The bit 8 of the data of register 30009 is the same as the data of register 00001.
The same is true for the optocoupler input.
Bit8 and bit9 of register 30003 and registers 10001 and 10002 all correspond to the specified
hardware.
The register address is in accordance with the PLC naming rules, the real address is to remove
the highest bit, and then subtract 1
Value
Baud rate
1
2400
2
4800
3
9600
4
19200
5
38400
Содержание CE-IO1600
Страница 1: ...1 13 CE IO1600 User Manual CE IO1600 Ethernet I O Module Manual...
Страница 8: ...8 13 CE IO1600 User Manual Open JYNetConfigEn it shows as below...
Страница 9: ...9 13 CE IO1600 User Manual Chosse Local connection Searching...
Страница 10: ...10 13 CE IO1600 User Manual Revise parameter researching...
Страница 12: ...12 13 CE IO1600 User Manual Check whether the IP to be modified by the device is occupied...
Страница 13: ...13 13 CE IO1600 User Manual Revise IP...
Страница 15: ...15 13 CE IO1600 User Manual 3 1 3 1 TCP Server 3 1 3 2 TCP Client Mode revisement...
Страница 17: ...17 13 CE IO1600 User Manual 3 1 3 3 UDP Server 3 1 3 4 UDP Client...
Страница 19: ...19 13 CE IO1600 User Manual Create a device oriented iP and port in TCP Client mode Send command test...
Страница 21: ...21 13 CE IO1600 User Manual Send command to test 3 2 2 3 UDP Server Mode Connection Example IO parameter...
Страница 24: ...24 13 CE IO1600 User Manual Send command to test After establishing communication the test is as below...
Страница 27: ...27 13 CE IO1600 User Manual...