Appendix B: Typical Runtime
20
ON Series m UPS User Instruction Manual
Appendix B:
Typical Runtime
Table 5. Typical Runtime by System Load
Typical Runtime by System
Load
ONm300 A, I and J Models
One 12V, 7AH Battery
ONm300D A, I and J Models
Two 12V, 7AH Batteries
VA LOAD
RUNTIME (HOURS:MINUTES)
75 VA
0:41
1:32
100 VA
0:21
1:09
150 VA
0:16
0:40
200 VA
0:10
0:30
250 VA
0:07
0:20
300 VA
0:05.
0:15
NOTE: Due to application specific conditions, your actual run time may be different.
Table 6. ON Series m 600 VA Extendable Runtimes
Typical Runtime
by System Load
ONm600X
Two 12 V, 7 AH
Batteries
Plus1
External
Battery
Plus2
External
Batteries
Plus 3
External
Batteries
Plus 4
External
Batteries
Plus 5
External
Batteries
VA LOAD
RUNTIME (HOURS:MINUTES)
100 VA
1:05
4:40
8:50*
10:30*
13:30*
16:40*
200 VA
0:35
2:40
5:00*
7:00*
9:00*
11:10*
400 VA
0:15
1:20
2:20*
3:30*
4:30*
5:30*
600 VA
0:05
0:30
1:10*
2:20*
3:00*
3:45
NOTE: Due to application specific conditions, your actual run time may be different.
NOTE: External Battery - Two 12V, 17AH per battery enclosure.
* Values shown are calculated.