Overview and Features
By connecting the power monitor/sensor KM series (sold separately), the ZN-KMX21-
□
allows you to record the measured data of the power monitor/sensor (KM series) and set
various operations.
●
Display and judgment output
The display of the measured data can be switched with the
▲
and
▼
keys. Also,
you can select the measurement target of the monitoring target and set the
threshold value to output an alarm from the output terminal.
●
Data output and viewing
Measurement values can be recorded to the unit's memory and the recorded
measurement values can be stored into the SD card.
SD card : Data is in CSV format.
Measured values collected on multiple sensors can be displayed as a graph and
combined as a single file by using the PC software that can be downloaded from
the product page.
■
Names and Functions
Display
MODE key
Item select key
( key)
Item select key
( key)
SET/REC/STOP key
Alarm output terminal
SD card slot
Sensor head
connector
AC adapter terminal
Mounting
screw hole
Reset switch
Screw hook hole
Function
Switches operating modes
Releases error and alarm (holding)
Cancels during settings
Moves setting items (upper direction)
Switches display screens (reverse direction)
Changes the setting value (increasing)
Moves the setting items (lower direction)
Switches the display screens (forward direction)
Changes the setting value (decreasing)
Confirms the setting value
Starts/stops record (holding)
Saves recorded data to the SD memory card.
Used to secure screws (M3x4 mm female hole)
For screw head hook
Restarts the unit.*
Name
MODE key
Item select key
( key)
Item select key
( key)
SET/REC/STOP key
Mounting screw hole
Screw hook hole
Reset switch
* Used when an SD card is not available when recording stops, or when error
recovery cannot be made.
LAN port
■
Alarm Output Specifications
GND
External
power
supply
OUT
0V
Load
GND OUT
●
Terminals
●
Output Specifications
Terminal names are inscribed on the unit.
For wire used for a terminal block,consider the following.
Wire length
:
30m and less
(1) OUT
Judgment result allocated in THR mode is output.
(2) GND
Common terminal.
Do not directly connect the external power supply between OUT and GND.
Be sure to connect the load.
External power
supply voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit
diagram
12 to 24 VDC
12 to 24 VDC ±10%
45 mA max.
1.2 V max.
0.1 mA max.
■
Display Unit
Display
Meaning and operation when turned on
Communication with LAN cable.
Integral power consumption reset interval is set.
The setting is OFF when it is not displayed.
LAN cable is connected and network communication is possible.
Recording data into the internal memory.
Recording start wait using timer when blinking.
Power is supplied.
Indicates the upper limit threshold value.
Indicates the maximum total momentary power value.
Indicates the minimum total momentary power value.
Indicates the average total momentary power value.
The unit is currently operating in RUN mode.
The unit is currently operating in FUN mode.
The unit is currently operating in THR mode.
SD card has been inserted.
SD card is being accessed while light blinking.
A total integrated power consumption has exceeded the specified
upper threshold value.
■
7-segment Display List
■
Ratings
Item
Connectable Power Sensor/Monitor
Model
KM20-B40-FLK, KM50-C, KM50-E, KM100, KM-N1-FLK, KM-N2-FLK and KM-N3-FLK
ZN-KMX21-
□
Accessories
10 to 150 Hz, 0.7 mm double amplitude, acceleration: 50 m/s2 for each in X, Y and Z directions for 80 min
*
7
150 m/s2 in 6 directions (+/-X, +/-Y, and +/-Z directions), 3 times each
*
7
Instruction Sheet (This sheet), Startup Guide,
Alarm Output Connector
*
7, AC Adapter
*
8,
*
9, DC Cable
*
9, and Dedicated Connection Cable
ABS
IP30
Magnet mounting, screw mounting, hook, free standing
Approx. 500 g
Shock Resistance
Material
Degree of Protection
Mounting
Weight (in Package)
Max. Number of Connectable
Power Sensor/Monitor Units
Display
Recording Interval
Recorded data
Operation Function
Recording Mode
External Output
Communication Interface
Memory Capacity (Internal)
Memory Capacity (External)
Power Supply
Current Consumption
Operating Temperature
Operating Humidity
Storage Humidity/Temperature
Insulation Resistance
Withstand Voltage
Vibration Resistance
7-seg. 5-digit 2-step LCD display, auxiliary information indicator displays
1 s, 2 s, 5 s, 10 s, 20 s, 30 s, 1 min.
Momentary power, Integrated power, Power factor, Sum of pulse input counts 1 and 2
*
1
Integrated power total sum, integrated momentary power, electricity rate total sum
Continue mode
*
2, Ring mode
*
3
Alarm output (Photocoupler output)
*
4
Ethernet (10BASE-T, 100BASE-TX)
Internal memory: approx. 200 data items (at maximum load); approx. 6800 data items*5 (at minimum load)
SD card with SDHC compatibility (measured value and converted value saving/set value saving and reading):
Recommended SD card: HMC-SD291(2GB)/HMC-SD491(4GB)(manufactured by OMRON) *6
DC input: 24 VDC±10%, AC adapter: 100 to 240 VAC/50 to 60 Hz
80 mA max. (at 24 VDC); 70 mA max. (AC adapter used)
Without Ethernet: -10°C to 40°C (no condensation or icing) With Ethernet: 0°C to 40°C (no condensation or icing)
20 to 85%RH (no condensation or icing)
-15°C to +60°C, 20 to 85%RH (no condensation or icing)
20 M
Ω
(500 VDC)
1000 VAC, 50/60 Hz, 1 min.
31 units
*
1: Only supported for KM50-C and KM50-E.
*
2: Automatically writes the data to the SD memory card when the internal memory reaches its capacity and continues recording until the SD card memory capacity reaches its limit. The
unit stops operation if there is no SD memory card inserted when the internal memory reaches its capacity. (Recording can be resumed after inserting an SD memory card and
outputting the data to it at a press of button.)
*
3: Continues the recording of the latest measured values until the internal memory reaches its capacity. (If the internal memory capacity exceeds the capacity, data is overwritten from
the oldest one in the memory.)
*
4: Output when the integrated power upper limit specified in THR mode is exceeded.
*
5: The maximum load is applied when 10 KM50-� units are connected; and the minimum load, when a single KM20-B40-FLK is connected.
*
6: When using third party SD card, please use industrial SD card (flash memory is SLC type) with high reliability and durability. Available SD card is SD standard or SDHC standard,
Class 4 or higher, (SDXC standard can not be used) You must confirm the operation of third party SD card yourself.
*
7: The vibration resistance when mounted using the ZN9-EM01-S magnets (separately sold): 10 to 55 Hz, 0.3mm double amplitude, acceleration: 20m/s2 for each in X, Y and Z
directions for 50 min. The installation place must be free from physical shock.
*
8: OMRON's XW4B-02B1-H1 connector.
*
9: This provided AC adapter must be used.
*
10: An AC adapter is provided in the ZN-KMX21 package; and a DC cable and ferrite core are included in the ZN-KMX21-A package.