background image

ZN-KMX21-

Power Sensor Station

© OMRON Corporation  

2011-2018

  All Rights Reserved.

Tighten the terminal screws at a recommended torque: 0.69 
to 0.88N·m. Make sure that the screws are not slanted away 
from the center after tightened.

40

2-4 Dia.

2-M3

60

56.8

117.2

24.6

0.7

48.6

49.4

40
60

■ 

Dimensions

PRECAUTIONS ON SAFETY

Indicates a potentially hazardous situation which, if 
not avoided, will result in minor or moderate injury, or 
may result in serious injury or death. Additionally 
there may be significant property damage.

This product uses a lithium battery that contains perchlorate that is 
regulated by California State Law. Appropriate measures must be taken to 
comply with regulations. 
For details, refer to the URL as below: 
www.dtsc.ca.gov/hazardouswaste/perchlorate

WARNING

Indicates a potentially hazardous situation which, if 
not avoided, may result in minor or moderate injury or 
in property damage.

● 

Meaning of Precaution Symbols

● 

Mandatory Requirement

Indicates a general mandatory requirement.

● 

Prohibition

Indicates general prohibition.

● 

Disassembly Prohibition

Indicates the possibility of accidents such as an electric shock 
caused by unit disassembly.

● 

Electric Shock Warning

Warns against an electric shock under specific conditions.

● 

Explosion Warning

Warns against an explosion under specific conditions.

CAUTION

● 

Perchlorate regulations by the State of California, USA

● 

Meanings of Signal Words

INSTRUCTION SHEET

Thank you for selecting OMRON product. This sheet primarily 
describes precautions required in installing and operating the product.
Before operating the product, read the sheet thoroughly to acquire
sufficient knowledge of the product. For your convenience, keep the
sheet at your disposal.

The mounting magnets provided with the product have 
strong magnetism. If the product is mounted using these 
magnets, anyone wearing a heart pacemaker must not 
operate the product; or the product must not be in proximity 
of such a person.

This product contains lithium batteries. Serious injury may 
occur due to fire or explosion. Do not attempt to 
disassemble the product, deform it by applying pressure, 

heat it in a high temperature (100°C℃ or more), or burn it 

for disposal.

● 

Warning Indications

WARNING

CAUTION

A minor or moderate injury or property damage may occur 
due to explosion. Do not use the product in an environment 
containing an inflammable or explosive gas.

An electric shock may occur. Do not replace the batteries 
when the unit is clamped to a conductor for measurement.

Observe the following precautions to ensure safe operation.

• Do not install the product in the places subject to exposure to water, oil, or chemical splashes.

• Only the provided AC adapter (not other) must be used when using AC power supply.

• If a voltage that exceeds the rated voltage is applied to the AC adapter, smoking may occur. Do 

not connect a power supply that exceeds the rated voltage. In a situation where a voltage 

higher than the rating is applied, use protective equipment so that the power supply voltage 

does not exceed the rated voltage.

• Dispose of the product as industrial waste.

• Do not let the product drop or subject it to a shock, which may cause its damage or malfunc-

tion. Use screws to secure the product when mounting it on the wall. Stop using the product if 

it has been applied with a strong impact.

• When inserting or removing an SD card, securely hold the product to prevent it from dropping, 

which may cause a damage. Do the same when inserting or detaching an AC adapter, alarm 

output cable, or sensor connector.

• Do not bring the product close to magnetic products (e.g. magnetic cards), sensitive electronics 

equipment (e.g. computers or clocks), when the product is attached with the mounting magnets.

• Small pieces may be chipped off the mounting magnets when they are attracted to the surface. 

Make sure the pieces do not enter the eyes. Consult a medical doctor if this happens.

• When using the mounting magnets to install the product, take caution not to allow a finger to 

be caught between the product(s) and the magnetic surface.

• Do not install the product at a high place when using the mounting magnets.

• Apply an appropriate load to the alarm output terminals to prevent possible smoking.

• If liquid crystal leaks due to a damage to the LCD panel, take caution not to allow it to contact 

your skin, to be inhaled or swallowed. If it has contacted your skin or entered your mouth, seek 

medical attention.

• Take anti-static electricity measures (e.g. touching grounded metal object) when handling the 

product.

 Applicable standards

    ・

EN61326-1

    ・

Electromagnetic environment : Industrial electromagnetic environment 

  

 

               

(EN/IEC

61326-1

Table 2)

PRECAUTIONS FOR SAFE USE

PRECAUTIONS FOR CORRECT USE

1. Avoid installing the product in the following places:

• Places exceeding the rated ambient temperature

• Places exposed to extreme temperature changes (where condensation occurs)

• Places subject to relative humidity exceeding the rated humidity range

• Places subject to corrosive or flammable gases

• Places subject to mist, droplets, coarse particles, fiber, salt, metal dust, or large amount of 

particles

• Places subject to direct shock or vibration

• Places subject to direct sunlight

• Places subject to exposure to water, oil, or chemical splashes

• Places subject to strong magnetic field or electric field

• Outdoors

2. Wiring

• Wire the product cable separately from high-voltage or power lines. Placing them in the same 

wiring or the same duct may cause induction, resulting in the product malfunction or damage.

• Make sure that the I/O terminals are inserted or removed with the power turned OFF. Doing 

this with the power ON may result in a failure.

• When using a DC cable, connect the white-lined wire of the cable to the power input (24 VDC 

± 3%) and the non-lined wire to 0V.

• Use a ferrite core to reduce the noise to/from other device when supplying power to the unit 

via a DC cable. To use the provided DC cable, attach the provided ferrite core as shown 
below.

3. Mounting screw holes

• 

 

The screw holes provided on the product are M3 and 4 mm deep. Do not screw deeper than 4 

mm, which may damage the product.

4. Operation

   When using the product, also read KM series power sensor/monitor instruction sheets for        

necessary information relevant to the product.

•  The Power Sensors/Monitors that can be connected to the product are KM20-B40-FLK, 

KM50-C, KM50-E, KM100, KM-N1-FLK, KM-N2-FLK and KM-N3-FLK.

   To directly connect KM-N1-FLK, KM-N2-FLK and KM-N3-FLK to ZN-KMX21- , please 

purchase a separately sold dedicated connection cable ZN9-KMC30-N. 

5.Long Term Storage

If the product will not be used for a long period of time, store the product in the location 

where the temperature is not too high. Otherwise the built-in battery may drain faster.

Screw hook holes dimensions 

Mounting hole process dimensions

Screw hook hole

Mounting screw hole 2-M3, 
4 mm in depth

Reset switch

LAN port

SD card slot

Alarm output terminal

Sensor head connector

Power supply 
input terminal 

MODE key

Select key 

(upper direction)

Select key 

(lower direction)

SET/REC/STOP key

Display

(Unit: mm)

Single winding

Portable Power Monitor unit side

approx. 100 mm

Power supply side

Model

The following notice applies only to products that carry the CE mark:
Notice:
This is a class A product. In residential areas it may cause radio 
interference, in which case the user may be required to take adequate 
measures to reduce interference.

Manufacturer:
  Omron Corporation,
  Shiokoji Horikawa, Shimogyo-ku,
  Kyoto 600-8530 JAPAN
 

TRACEABILITY INFORMATION:
Importer in EU:
  Omron Europe B.V.
  Wegalaan 67-69
  2132 JD Hoofddorp,
  The Netherlands

* 9 5 2 1 9 5 8 - 0 G *

Отзывы: