217
High-speed Counters
Section 5-2
5-2-3
Procedure
Select high-speed counter 0 to 3.
Select the pulse input method, reset
method, and counting range.
Select the kind of interrupt (if any).
Wire inputs.
PLC Setup settings
Ladder program
•
Pulse input methods: Differential phase (4x), Pulse +
direction, Up/Down, or Increment
•
Reset methods: Phase-Z + Software reset, Software
reset, Phase-Z + Software reset (continuing comparing),
Software reset (continuing comparing)
•
Counting ranges: Linear mode or Ring mode
•
Enable/disable interrupts
•
Target value comparison interrupt
•
Range comparison interrupt
•
Connect to the terminals (24 VDC input or line-
driver)
•
High-speed Counters 0 to 3 Enable/Disable:
•
High-speed Counters 0 to 3Pulse Input Mode:
Differential phase (4x)
Pulse + direction
Up/Down
Increment
•
High-speed Counters 0 to 3 Reset Method:
Phase-Z + Software reset, Software reset, Phase-Z + Software
reset (continuing comparing), Software reset (continuing
comparing)
•
High-speed Counters 0 to 3 Counting Mode:
Linear mode
Ring mode
•
Program the interrupt task (with any interrupt number between 0
and 255) to be executed when using a target value comparison
or range comparison interrupts.
•
Register a target value comparison table and start the
comparison.
•
Register a range comparison table and start the comparison.
•
Register a target value comparison table without starting the
comparison.
•
Register a range comparison table without starting the
comparison.
•
Change the counter PV.
•
Start comparison with the registered target value comparison
table or range comparison table.
•
Read the high-speed counter PVs, read the status of the high-
speed counter comparison operation, or read the range-
comparison results.
•
Turn ON the High-speed Counter Gate Bit to stop counting input
pulses.
•
High-speed counters 0 to 3 on X/XA CPU Units and high-speed
counters 2 and 3 on Y CPU Units: 24 VDC input, Response
frequency: 50 kHz for single-phase, 100 kHz for differential phase
•
High-speed counters on Y CPU Units: Line-driver input, Response
frequency: 500 kHz for single-phase, 1 MHz for differential phase
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......