Section 6
Power Considerations
47
Grounding Connections
Screw (4 mm head with
selfraising pressure plate)
3G2A5-PS223-E/221-E/213-E
3G2A5-PS222-E/212-E
Screw (4 mm head with
selfraising pressure plate)
For grounding use 2mm
2
cable.
Be sure to keep the length of the
cable less than 20 meters.
8.6 mm max.
8.6 mm max.
Be sure to use a wire of at least 1.25 mm
2
in thickness.
Use M4 screws for tightening crimp terminals. Use crimp terminals
for wiring. Do not connect bare stranded wires directly to terminal
blocks.
Tighten the terminal block screws to a torque of 1.2 N
S
m.
Caution
Ground the Power Supplies separately from peripheral devices.