Section 5
Installation Environment
41
5-4
Preventing Noise
In order to prevent noise from interfering with the operation of the PC, use
AWG 14 twisted-pair cables (cross-sectional area: 2 mm
2
min.). Avoid mount-
ing the PC close to high-power equipment, and make sure the point of instal-
lation is at least 200 mm away from power cables as shown below.
PC
200 mm min.
200 mm min.
Power lines
Whenever possible, use wiring conduit to hold the I/O wiring. Standard wiring
conduit should be used, and it should be long enough to completely contain
the I/O wiring and keep it separated from other cables.