3-4
Section
IR and DM Areas
47
For normal mode, set the operation mode switch on the rear panel of the Unit as
shown in the following diagram.
The allocation of IR words and bits is shown in the following table.
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU
n
Not used.
Conversion enable outputs
p
(CPU to
Unit)
8
7
6
5
4
3
2
1
Unit)
n+1
Output 1 set value
16
3
16
2
16
1
16
0
n+2
Output 2 set value
n+3
Output 3 set value
n+4
Output 4 set value
n+5
Output 5 set value
n+6
Output 6 set value
n+7
Output 7 set value
n+8
Output 8 set value
Input
(Unit to
n+9
Error code
Output setting error outputs
(Unit to
CPU)
16
1
16
0
8
7
6
5
4
3
2
1
Note
For the IR word addresses, n = 100 + 10 x unit number.
For Units #A to #F (10 to 15), n = 400 + 10 x (unit number – 10).
Set Values and Stored Values
Item
Contents
Conversion enable
0:
Stop conversion output
1:
Begin conversion output
Set value
16-bit binary data
Output setting error
0:
No error
1:
Output setting error
Error code
Two digits, hexadecimal (00 for no error)
Allocation for Normal
Mode
Содержание SYSMAC C200H-AD003
Страница 1: ...Cat No W325 E1 04 Analog I O Units SYSMAC C200H AD003 DA003 DA004 MAD01...
Страница 2: ...C200H AD003 DA003 DA004 MAD01 Analog I O Units Operation Manual Revised June 2003...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 145: ...Cat No W325 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...