1-2
Section
Basic Configuration
6
Mounting Analog I/O Units
Use the following procedure to mount an Analog I/O Unit to the Backplane.
1, 2, 3...
1. Lock the top of the Analog I/O Unit into the slot on the Backplane and rotate
the Unit downwards as shown in the following diagram.
Hook
Backplane
Lock lever
2. While making sure to align the Unit properly with the connectors, press
down on the lock lever at the bottom of the slot, press the Unit firmly into po-
sition, and then release the lock lever.
(To remove a Unit, hold down the lock lever with an implement such as a
screwdriver.)
Lock lever
Leave enough space below each Rack, as shown in the following diagram for
mounting and removing the Units.
20 mm min.
20 mm min.
Backplane
Flat-blade screwdriver
Precautions
Be sure to turn off the power supply to the PC before installing or disconnecting
Units or connecting lines.
To reduce the risk of malfunctioning due to electrical noise, wire input and output
lines in separate ducts from high-voltage and power lines.