Do not touch the Inverter fins, braking resistors and the motor, which
become too hot during the power supply and for some time after the
power shutoff. Doing so may result in a burn.
CAUTION
The Inverter has high voltage parts inside which, if short-circuited,
might cause damage to itself or other property. Place covers on the
openings or take other precautions to make sure that no metal objects
such as cutting bits or lead wire scraps go inside when installing and
wiring.
Install a stop motion device to ensure safety. Not doing so might result
in a minor injury. (A holding brake is not a stop motion device designed
to ensure safety.)
Be sure to use a specified type of braking resistor / regenerative
braking unit. In case of a braking resistor, install a thermal relay that
monitors the temperature of the resistor. Not doing so might result in a
moderate burn due to the heat generated in the braking resistor /
regenerative braking unit. Configure a sequence that enables the
Inverter power to turn off when unusual overheating is detected in the
braking resistor / regenerative braking unit.
Do not connect resistors to the terminals (+1, P/+2, N/-) directly.
Doing so might result in a small-scale fire, heat generation or damage
to the unit.
Do not dismantle, repair or modify the product.
Doing so may result in an injury.
Take safety precautions such as setting up a molded-case circut
breaker(MCCB) that matches the Inverter capacity on the power
supply side. Not doing so might result in damage to property due to
the short circuit of the load.
Precautions for Safe Use
Installation and Storage
Do not store or use the product in the following places.
x
Locations subject to direct sunlight.
x
Locations subject to ambient temperature exceeding the specifications.
x
Locations subject to relative humidity exceeding the specifications.
x
Locations subject to condensation due to severe temperature fluctuations.
x
Locations subject to corrosive or flammable gases.
x
Locations subject to exposure to combustibles.
x
Locations subject to dust (especially iron dust) or salts.
x
Locations subject to exposure to water, oil, or chemicals.
x
Locations subject to shock or vibration.
Transporting, Installation and Wiring
x
Do not drop or apply a strong impact on the product.
Doing so may result in damaged parts or malfunction.
x
Do not hold by the front cover, but hold by the fins during transportation.
x
Do not connect an AC power supply voltage to the control input / output
terminals. Doing so may result in damage to the product.
x
Be sure to tighten the screws on the terminal block securely. Wiring work
must be done after installing the unit body.
x
Do not connect any load other than a three-phase inductive motor to the
U, V and W output terminals.
x
Take sufficient shielding measures when using the product in the following
locations. Not doing so may result in damage to the product.
Locations subject to static electricity or other forms of noise.
Locations subject to strong magnetic fields.
Locations close to power lines.
Operation and Adjustment
x
Be sure to confirm the permissible range of motors and machines before
operation because the inverter speed can be changed easily from low to
high.
x
Provide a separate holding brake if necessary.
Maintenance and Inspection
x
Be sure to confirm safety before conducting maintenance,
inspection or parts replacement.
x
Mount the product vertically on a wall or on a DIN Rail(optional) with the
product’ s longer sides upright.
The material of the wall has to be nonflammable such as a metal plate.
x
Confirm that the rated input voltage of the Inverter is the same as AC
power supply voltage.
Precautions for Correct Use
Installation
Main Circuit Power Supply
Error Retry Function
x
Do not come close to the machine when using the error retry function
because the machine may abruptly start when stopped by an alarm.
x
Be sure to confirm the RUN signal is turned off before resetting the alarm
because the machine may abruptly start.
Operation Stop Command
Non-Stop Function at Momentary Power Interruption
x
Provide a separate emergency stop switch because the STOP Key on the
Operator is valid only when function settings are performed.
x
When checking a signal during the power supply and the voltage is
erroneously applied to the control input terminals, the motor may start
abruptly. Be sure to confirm safety before checking a signal.
Product Disposal
x
Comply with the local ordinance and regulations when disposing of the product.
UL Cautions
The warnings and instructions in this section summarizes the procedures
necessary to ensure an inverter installation complies with Underwriters
Laboratories guidelines.
x
Use 60/75°C Cu wire only.
(For models: A2015, A2022, A2037, A2055, A2075, AE007, AE015,
AE022)
x
Use 75°C Cu wire only.
(For models: A2002, A2004, A2007, A4022, A4037, A4055, A4075,
AE002, AE004)
x
Use 60°C Cu wire only.
(For models: A4004, A4007, A4015)
x
Open Type Equipment.
x
Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 240 V maximum when protected by Class J fuses.
(For models: -A2055 and -A2075)
x
Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 240V maximum when protected by Class CC, G, J
or R fuse or circuit breaker having an interrupting rating not les than
100,000 rms symmetrical amperes, 240 volts maximum.
(For models: 200V class except models with -A2055 or -A2075)
x
Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 480V maximum when protected by Class CC, G, J
or R fuse or circuit breaker having an interrupting rating not les than
100,000 rms symmetrical amperes, 480 volts maximum.
(For models: 400V class)
x
Install device in pollution degree 2 environment.
x
Maximum Surrounding Air Temperature 50°C.
x
Caution-Risk of electric shock, capacitor discharge time is at least 5
minutes.
x
Solid State motor overload protection is provided in each model.
x
Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with
the National Electric Code and any additional local codes.
x
Motor over temperature protection is not provided by the drive.
Circuit breaker and Fuse Size
Terminal Tightening Torque and Wire Size
Conformance to EU Directives
OMRON Corporation
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530, Japan
Omron Europe B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp, The Netherlands
x
Do not come close to the machine when selecting restart in the non-stop
function at momentary power interruption selection(b050) because the
machine may abruptly start after the power is turned on.
NT302XE
The wire size range and tightening torque for field wiring terminals are
presented in the tables below.
200V
(class)
400V
(class)
0.75
7 1/2
14
(75°C only)
16
(60°C only)
14
(75°C only)
12
0.2
Inverter Model
(3G3JX-)
Input
Voltage
kW
HP
Power
Terminal
Wiring Size
Range
(AWG)
Torque
Ft·lbs
(N·m)
Motor
Output
1/4
A2002/AE002
0.4
1/2
A2004/AE004
1
A2007
0.75
1
AE007
1.5
2
AE015
1.5
2
A2015
0.6
0.8
12
2.2
3
AE022
2.2
3
A2022
3.7
5
A2037
5.5
A2055
10
7.5
A2075
0.75
7 1/2
0.4
1/2
A4004
1
A4007
1.5
2
A4015
2.2
3
A4022
3.7
5
A4037
5.5
A4055
10
7.5
A4075
10
0.9
1.2
0.9
1.2
8
2.3
3.0
2.3
3.0
Wire Connectors
Field wiring connections must be made by a UL Listed and CSA certified
ring lug terminal connector sized for the wire gauge being used. The
connector must be fixed using the crimping tool secified by the connector
manufacturer.
Terminal(ring lug) Cable support
Cable
The Inverter’ s connection to input power must include UL Listed inverse
time circuit breakers with 600V rating, or UL Listed fuses as shown in the
table below.
Input
Voltage
Inverter Model
(3G3JX-)
Circuit Breaker / Fuse
Ratings
(A)
200V
(class)
400V
(class)
A2002/AE002
A2004/AE004
A2007/AE007
AE015
AE022
A2022
A2037
A2055
A2075
A4004
A4007
A4015
A4022
A4037
A4055
A4075
Inverse time
circuit Breaker
Distribution Fuse
(Class J)
10
15
A2015
20
30
40
50
3
6
10
15
20
25
Motor Overload Protection
3G3JX Inverters provide solid state motor overload protection, which
depends on the proper setting of the following parameters .
x
b012 : electronic overload protection
x
b212 : electronic overload protection, 2nd motor
Set the rated current [Amperes] of the motor(s) with the above
parameters. The setting range is 0.2 rated current to 1.0 rated current.
When two or more motors are connected to the Inverter, they cannot be
protected by the electronic overload protection. Install an external thermal
relay on each motor.
x
For earthing, selection of cable, and any other conditions for
EMC-compliance, please refer to the User’ s manual for installation.
x
This is a class A product in residential areas it may cause radio
interference, in which case the user may be required to take adequate
measures to reduce interference.
3G3JX series Inverter has integrated EMC filter as
shown below
x
200V class : EN61800-3 category C1
x
400V class : EN61800-3 category C2
0193670-5C
Terminal
Conector
Wiring Size
Range(AWG)
Torque
Logic and Analog
connectors
30-16
30-14
0.16-0.19 0.22-0.25
Relay connector
0.37-0.44
0.5-0.6
Ft·lbs
(N·m)
Inverse time
circuit Breaker
AVERTISSEMENT: ne retirez pas le capot avant pendant l’alimentation
et 5 minutes après l’arrêt de l’alimentation. Cela peut entraîner de
grave blessure due à un choc électrique.
For KC Marking Only
ἽGὤὤ
ஂ㛹ⱨ㟝Gⵝ㋕䋩㐔ὤ㣄㣠ஃ
G
㢨Gὤὤ⏈G㛹ⱨ㟝OἽPG㤸㣄䑀㤵䚝ὤὤ⦐㉐G䑄⬘㣄G❄⏈G㇠㟝㣄⏈G㢨G
㥄㡸G㨰㢌䚌㐐ὤGⵈ⢰⮤SGᴴ㥉㞬㢌G㫴㜡㜄㉐G㇠㟝䚌⏈Gᶷ㡸G⯝㤵㡰⦐G
䚝⏼␘U
SUITABILITY FOR USE
Omron Companies shall not be responsible for conformity
with any standards, codes or regulations which apply to
the combination of the product in the buyer’s application
or use of the product.
At buyer’s request, Omron will provide applicable third party certification
documents identifying ratings and limitations of use which apply to the product.
This information by itself is not sufficient for a complete determination of the
suitability of the product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining
appropriateness of the particular product with respect to Buyer’s application,
product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY
RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
EQUIPMENT OR SYSTEM.
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD
Hoofddorp
The Netherlands
Tel: (31)2356-81-300
Fax: (31)2356-81-388
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08
(Lobby 2), Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011
Fax: (65) 6835-2711
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900
Fax: (1) 847-843-7787
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
Pu Dong New Area, Shanghai,
200120, China
Tel: (86) 21-5037-2222
Fax: (86) 21-5037-2200
Note:
Specifications subject to change without notice.
OMRON Corporation
Industrial Automation Company
m
o
c
.
n
o
r
m
o
.
a
i
.
w
w
w
:
t
c
a
t
n
o
C
Tokyo, JAPAN