163
Status Areas
Section 6-2
Alarm Status Area
A Temperature Input Unit’s Alarm Status Area is configured of the following 16
bits. The Alarm Status Area provides notification of serious errors in the Unit.
5
Reserved.
---
6
Reserved.
---
7
Reserved.
---
8
Temperature Input Warning
Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the temperature data
exceeds the range that can be dis-
played or the monitoring value set for
the comparator function.
9
Cumulative Counter Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the cumulative value
exceeds the monitoring set value.
10
Data Comparison between
Channels Threshold Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the temperature differ-
ence between input channels exceeds
the monitoring set value.
11
Temperature Range Total
Time Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the present value being
counted in the set range exceeds the
monitoring set value.
12
Top/Valley Count Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the top or valley count
exceeds the monitoring set value.
13
Reserved.
---
14
Reserved.
---
15
Reserved.
---
Bit
Contents
Description
Bit
Contents
Description
0
Reserved.
---
1
EEPROM data error
OFF: Normal; ON: Error
2
Reserved.
---
3
Reserved.
---
4
Reserved.
---
5
Reserved.
---
6
Reserved.
---
7
Reserved.
---
8
Off-wire Detection Flag
Turns ON when a sensor is discon-
nected or a cold junction compensator
error occurs.
OFF: Normal or the input error detec-
tion disabled setting is set to disable
detecting input errors.
ON: Disconnection or cold junction
compensator error
Содержание SmartSlice GRT1-Series
Страница 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Страница 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xiv ...
Страница 21: ...xxii EC Directives 6 ...
Страница 63: ...42 Connecting Turnback Cables Section 3 3 ...
Страница 109: ...88 Digital I O Units Section 4 6 ...
Страница 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Страница 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Страница 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Страница 323: ...302 Troubleshooting by Unit Section 9 5 ...
Страница 351: ...330 Explicit Messages Appendix A ...
Страница 355: ...334 Power Consumption and Weight Tables Appendix C ...
Страница 357: ...336 I O Current Consumption Table Appendix D ...
Страница 365: ...344 Revision History ...