163
Status Areas
Section 6-2
Alarm Status Area
A Temperature Input Unit’s Alarm Status Area is configured of the following
16 bits. The Alarm Status Area provides notification of serious errors in the
Unit.
4
Reserved.
---
5
Reserved.
---
6
Reserved.
---
7
Reserved.
---
8
Temperature Input Warning
Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the temperature data
exceeds the range that can be dis-
played or the monitoring value set for
the comparator function.
9
Cumulative Counter Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the cumulative value
exceeds the monitoring set value.
10
Data Comparison between
Channels Threshold Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the temperature differ-
ence between input channels exceeds
the monitoring set value.
11
Temperature Range Total
Time Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the present value
being counted in the set range exceeds
the monitoring set value.
12
Top/Valley Count Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or above
monitoring set value)
Turns ON when the top or valley count
exceeds the monitoring set value.
13
Reserved.
---
14
Reserved.
---
15
Reserved.
---
Bit
Contents
Description
Bit
Contents
Description
0
Reserved.
---
1
EEPROM data error
OFF: Normal; ON: Error
2
Reserved.
---
3
Reserved.
---
4
Reserved.
---
5
Reserved.
---
6
Reserved.
---
7
Reserved.
---
Содержание SMARTSLICE GRT1-DRT
Страница 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Страница 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 20: ...xx EC Directives 6 ...
Страница 62: ...42 Connecting Turnback Cables Section 3 3 ...
Страница 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Страница 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Страница 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Страница 322: ...302 Troubleshooting by Unit Section 9 5 ...
Страница 350: ...330 Explicit Messages Appendix A ...
Страница 354: ...334 Power Consumption and Weight Tables Appendix C ...
Страница 356: ...336 I O Current Consumption Table Appendix D ...
Страница 364: ...344 Revision History ...
Страница 365: ......