1.3.  [UPS Management] Menu 

 
 

・ 

The controllable parameter information on an uninterruptible power supply (UPS) that 
the SNMP/Web card was inserted is displayed and set up. 

・ 

The user can browse all those sub menus by read-only. 

・ 

Read-write access is granted only to the system administrator. 

 

 

[UPS Configuration] Menu

 

 

・ 

Display and set the main operation of uninterruptible power supply (UPS). 

 

Before login 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

After login 

 

12 

 

Содержание SC20G2

Страница 1: ...ONS Co Ltd To copy reproduce and reprint the contents partially oron the whole without notice to our company is refused firmly The contents of this document are subject to change without notice About a picture it may differ from the newest thing in part Windows and other names are the registered trademarks of U S Microsoft Corporation in the U S and other countries Each other company names and eac...

Страница 2: ...It is possible to shut down by setup in the following cases When a main power supply system is downed When the battery of an uninterruptible power supply UPS falls When the connection capacity of an uninterruptible power supply UPS exceeds When the temperature of an uninterruptible power supply UPS rises Automatic shutdown software and a script shutdown can perform schedule operation A computer ca...

Страница 3: ... abnormal condition 71 2 5 Schedule shutdown 73 2 6 Setting of remote shutdown 76 3 Management by SNMP 80 3 1 Access control of a SNMP Web card 80 3 2 A setup of an SNMP trap addressee 80 3 3 SNMP manager s setup 80 4 The monitor of the log by a JAVA applet 81 4 1 Feature 81 4 2 The display of a monitoring screen 81 4 3 Details of a UPS data log screen 82 4 4 Details of a UPS extended history log ...

Страница 4: ...t the setting method of the IP address of a SNMP Web card Please refer to 3 3 Network Configuration Method 2 via Telnet or 3 2 Network Configuration Method 1 via serial port of installation section in operation manual 3 The screen for a setup of a SNMP Web card is displayed In order to check the detailed information of each screen click Help under a screen Please click the menu of the upper part a...

Страница 5: ...er can browse all those sub menus by read only Main Page Menu The basic operating state of the present uninterruptible power supply UPS is displayed by list In order to set up the update time of this screen please carry out by SNMP Web card management SNMP Web card configuration Page Refresh Rate Sec 3 ...

Страница 6: ... test UPS Fail This is a state in which some abnormality is detected in uninterruptible power supply UPS UPS not Found SNMP Web card cannot communicate with the uninterruptible power supply UPS 3 UPS Temperature Displays the temperature of internal uninterruptible power supply UPS 4 UPS Manufacture OMRON is displayed 5 OutletA B C Control sec Display the used time of each output of the uninterrupt...

Страница 7: ...etup is displayed 15 UPS Next On Time The schedule of the next uninterruptible power supply UPS power supply On by schedule operation setup is displayed 16 SNMP Web Card Firmware Revision It is a version of firmware 17 SNMP Web Card System Date A system date setup of a SNMP Web card is displayed 18 SNMP Web Card System Time A system time setup of a SNMP Web card is displayed 19 SNMP Web Card Up Ti...

Страница 8: ...ate of the input power output power and a battery of the present uninterruptible power supply UPS is displayed This page is automatically updated in Page Refresh Rate Sec time which can be set up at SNMP Web card management 6 ...

Страница 9: ...ime is displayed 4 InputFrequency The present input frequency is displayed Battery Parameters 1 BatteryStatus The state of a battery is displayed by the following contents Normal Battery Low Discharging Battery aging Not Connected 2 Time since on Battery Power The time which is operating by battery power is displayed 3 Battery CapacityRemaining The remaining battery capacity of the present to a fu...

Страница 10: ... setup and an uninterruptible power supply UPS outlet control function can be displayed according to an each outlet Overall operation of each outlet is checked with this chart The detail description of a screen 1 UPS Outlet Information The time chart according to outlet is displayed This screen is only a display 8 ...

Страница 11: ...ard configuration The detail description of a screen 1 Number of Active Alarms The number of factors with which the present alarm is sounded is displayed 2 Alarm Time The time that each alarm was sounded Display time follows a setup of a SNMP Web card 3 Alarm Description It is a factor of sounding the alarm For the past alarms it is stored in the log 9 ...

Страница 12: ...on of a screen 1 Connected Client Number It is the number of clients under present operation 2 IP Address It is an IP address of a client 3 Client Name It is a computer name of a client 4 Shutdown Delay It is processing time required in order to terminate the application set as the shutdown of a client Please refer to the uninterruptible power supply UPS management shutdown setting for the time se...

Страница 13: ... computer name which has installed SC20G22 or the master agent of PowerActPro is displayed Slave The computer name which has installed the slave agent of PowerActPro is displayed 2 Model UPS model is displayed 3 UPS Status The state of UPS is displayed 4 BatteryStatus The state of a battery is displayed 5 CommunicationStatus A communication state is displayed 11 ...

Страница 14: ...UPS that the SNMP Web card was inserted is displayed and set up The user can browse all those sub menus by read only Read write access is granted only to the system administrator UPS Configuration Menu Display and set the main operation of uninterruptible power supply UPS Before login After login 12 ...

Страница 15: ...Set Point It is a maximum of the load of an uninterruptible power supply UPS When the connection capacity of an uninterruptible power supply UPS exceeds this value a SNMP Web card operates an uninterruptible power supply UPS according to a setup of an uninterruptible power supply UPS shutdown menu 8 Voltage Detect Level Only line interactive type The voltage sensitivity of an uninterruptible power...

Страница 16: ...ntrol Menu The immediate stop and reboot of an uninterruptible power supply UPS can be performed Some items can browsed by the access authority holder which can be read and written Before login After login 14 ...

Страница 17: ... Time The delay time to an uninterruptible power supply UPS stop is set up after clicking execute It becomes a common setting of UPS management shutdown setting screen 5 Turn On UPS Cancel UPS Shutdown The halt condition of an uninterruptible power supply UPS is canceled and started When power supply Off is manually carried out from the front panel of an uninterruptible power supply UPS it cannot ...

Страница 18: ...est and a function test are set up A short time about 10 seconds simple battery test is included in a function test Some items can browsed by the access authority holder which can be read and written Before login After login 16 ...

Страница 19: ...st 3 Last Test Result It is the last battery test result Self Test 1 Self Test The enable disable of a test is set up 2 Last Test Start Time It is the implementation date of the previous test 3 Last Test Result It is the last battery test result Backup Time Test Only line interactive type 1 Backup Time Test The enable disable of a test is set up 2 Last Test Start Time It is the implementation date...

Страница 20: ... UPS Test Schedule Menu The schedule for a test is displayed and set up Before login After login 18 ...

Страница 21: ...et up a test execution day in a week 2 TestTime Please set the test execution time 3 TestAction Please specifies one of the following whether you carry out the self test Backup time test A backup time test is done Self test A self diagnosis test is done 19 ...

Страница 22: ... Shutdown Setting Menu The parameter at the time of performing the shutdown of a computer and a stop of an uninterruptible power supply UPS is set Before login After login 20 ...

Страница 23: ...ring is displayed and set up A detail description of Shutdown Actions 1 Disabled Nothing operates 2 Warning A warning message is transmitted to a client A shutdown a stop etc are not performed 3 Client Shutdown A shutdown command is sent out to a client computer A stop of an uninterruptible power supply UPS is not performed 4 UPS Turn Off An uninterruptible power supply UPS stop is performed after...

Страница 24: ...rt condition Battery capacity and UPS initiation delay time are specified Battery Level Required charging capacity is set up at a start up When the power down occurred immediately after unless there is sufficient capacity for a shutdown since it is dangerous it does not start unless charge is completed to specification capacity Output Start Delay Time of UPS Boot Up Please set up time until the ou...

Страница 25: ...lace Date It is the last battery exchange day 4 BatteryUnit It is the number of battery unit of uninterruptible power supply UPS 5 UAS0 It is the maintenance information about UPS 6 UOS It is the maintenance information about UPS 7 DIC It is the maintenance information about UPS 8 RRTC It is the maintenance information about UPS 9 TOT It is the maintenance information about UPS 10 TBN It is the ma...

Страница 26: ...te shutdown with multiple uninterruptible power supplies UPS is set up It is used when backing up an uninterruptible power supply UPS and storage with a respectively different uninterruptible power supply UPS Before login After login 24 ...

Страница 27: ...upply UPS of only one of either 4 Notify Master UPS Ignore information from Slave UPS By setup only a master or a slave uninterruptible power supply UPS goes into stop operation The operation in the case of a stop follows a shutdown setting 5 NotifyALL All the uninterruptible power supplies UPS that have a cooperation relation a master slave relations go into stop operation In any case stop operat...

Страница 28: ...a week unit is performed Please determine operation on a UPS management shutdown setting screen after a setup by this page When set up correctly it is displayed on UPS monitor UPS main page as a UPS next Off On time Before login After login 26 ...

Страница 29: ... UPS is set up per day of the week 2 ShutdownTime The time which halts an uninterruptible power supply UPS is set up 3 Restart Day The day which starts an uninterruptible power supply UPS is set up per day of the week 4 Restart Time The time which starts an uninterruptible power supply UPS is set up 27 ...

Страница 30: ... Special Day Schedule Menu A schedule setup of a special day is performed Please determine operation on a UPS management shutdown setting screen after a setup by this page Before login After login 28 ...

Страница 31: ...uptible power supply UPS is set up 2 ShutdownTime The time which halts an uninterruptible power supply UPS is set up 3 Restart Day The day which starts an uninterruptible power supply UPS is set up 4 Restart Time The time which starts an uninterruptible power supply UPS is set up 29 ...

Страница 32: ...mation about the control parameter of a SNMP Web card is displayed and set up Read write access is granted only to the system administrator Date and Time Menu The system time of a SNMP Web card is displayed and set up Before login After login 30 ...

Страница 33: ...ime of the SNMP Web card will be synchronized with the time on the computer It will perform synchronization when you press the Save It does not even attempt to synchronization periodically thereafter 4 Synchronize with NTP server The system time of a SNMP Web card is synchronized with a NTP server It synchronizes when preservation is pushed and it synchronizes every 6 hours after that 5 Set manual...

Страница 34: ... SNMP Web Card Configuration Menu The network parameter of a SNMP Web card is displayed and set Before login After login 32 ...

Страница 35: ...ed Please set if necessary 7 System Location System Location specified to MIB II is displayed Please set if necessary 8 Battery Last Replaced Date The date the beginning of use exchange the battery in uninterruptible power supply UPS Please re set when you make a new battery replacement 9 History Log Interval This is the time interval to record log data log of output voltage connected load such as...

Страница 36: ...ddress When you use IP by fix please set to enable 14 Telnet Connection Enable disable of telnet connection are displayed and set up 15 SNMP Function Enable disable of an SNMP function are displayed and set up 16 SNMP Version The version of SNMP used for SNMP connection is displayed and set up 17 Network Upgrade Enable disable of the firmware upgrade via a network are displayed and set up 18 Broad...

Страница 37: ... SNMP Web Card Control Menu Restart reboot of a SNMP Web card and reset of an internal parameter can be performed Before login After login 35 ...

Страница 38: ...hen you reset the parameter of a SNMP Web card to the initial value at the time of factory shipments 2 Restart SNMP Web Card Please choose when you restart a SNMP Web card 3 Same Setting With Please set up the IP address of equipment which refers to the parameter of a SNMP Web card 36 ...

Страница 39: ... Syslog Configuration Menu A Syslog function is displayed and set up Before login After login 37 ...

Страница 40: ...y of a Syslog function is displayed and set up 3 Syslog server The IP address of a Syslog server is displayed and set up 4 Map to Syslog s Severity The information level at the time of sending out to a Syslog server about information level Severe and Warning and Informational on a SNMP Web card respectively is specified 38 ...

Страница 41: ... Port Number Configuration Menu The port number of SNMP HTTP and Telnet is displayed and set up Before login After login 39 ...

Страница 42: ... SNMP Web Access Control Menu The IP address of NMS computer in which the read write by SNMP HTTP to a SNMP Web card is enable is displayed and set up Before login After login 40 ...

Страница 43: ...mple When 192 168 7 255 is set up it means that the ranges from 192 168 7 0 to 192 168 7 255 of IP address were set up 2 Community The community of the set up IP address is set up 3 AccessType It can set up from three kinds of not access read read write Please refer to 5 About security setting for detailed information on how to use the access control 41 ...

Страница 44: ... SNMP V3 Access Control Menu A setup at the time of communicating using SNMP V3 is performed to SC20G22 Before login After login 42 ...

Страница 45: ...o set up 3 SecurityLevel The security level of the user who set up can be set up from three kinds of noAuthNoPriv authNoPriv and authPriv Please use the same setup as the SNMP manager that performs communication with SC20G22 4 Authentication An authentication method can be set up from two kinds HMAC MD5 and HMAC SHA Please use the same setup as the SNMP manager that performs communication with SC2...

Страница 46: ... SNMP TRAP Receivers Menu The addressee of an SNMP trap is displayed and set up Before login After login 44 ...

Страница 47: ...RFC 1628 trap SWC trap SNMP Web Card trap 4 Severity The level of the trap which transmits can be set up from the following three items Informational All the traps are transmitted Warning The trap more than a Warning level is transmitted Example When load exceeds a preset value and it changes to battery mode etc Severe The trap of a warning level is transmitted Example uninterruptible power supply...

Страница 48: ...pparatus connected to UPS is registered and it supervises by Ping to the IP address of apparatus and performs a setup which controls shutdown operation of SC20G2 according to the success or failure of Ping Before login After login 46 ...

Страница 49: ... occur to Ping monitoring It can choose from five items of output stop an output stop and start a UPS stop a UPS stop and start continue If UPS stop or UPS stop and start is chosen by the outlet A the outlet B and the outlet C will stop an output according to a UPS stop 6 Pass Rate Among the Ping test in which they are tried it will specify the number of times of response which can be judged as pa...

Страница 50: ... Menu The MAC Address which transmits a WakeOnLAN packet is registered It is used when rebooting two or more client PCs simultaneously at the time of an uninterruptible power supply UPS reboot Before login After login 48 ...

Страница 51: ...N packet is set up 4 MAC Address The addressee MAC Address of a WakeOnLAN packet is set up 5 Action The reception site operation at the time of WakeOnLAN packet reception is set up 6 Description The information of an addressee including computer name etc is set up Attention A WakeOnLAN function may be unable to be used with PC of use For details please refer to P91 the network adapter setting meth...

Страница 52: ...Script Shutdown Menu Set the shutdown operation which does not depend on the presence of automatic shutdown software by sending the script to the devices connected to the UPS Before login After login 50 ...

Страница 53: ...gin failure 7 Time Out sec It is arbitrarily sets up the timeout time in the case of login 8 Wait time for run script Sec It delays the start time of script shutdown 9 Select Script Number The script performed when SC20G2 starts shutdown operation is specified A script is set up by the following clause a script setup 11 Protocol It specifies the communication method used by the SC20G2 It supports ...

Страница 54: ... Script Setting Menu The script which transmits to the apparatus connected to UPS is set up Before login After login 52 ...

Страница 55: ...s follows As for the contents all are execution about the shutdown operation after logging in to object apparatus Please refer to the following when operation becomes unstable Script 1 Windows rcv login snd u1 rcv password snd p1 rcv C snd shutdown s f Script 2 Linux rcv login snd u1 rcv Password snd p1 rcv snd u2 rcv Password snd p2 rcv snd init 0 Script 3 UNIX rcv login snd u1 rcv Password snd p...

Страница 56: ...v snd stop h f Script 6 Netapp rcv login snd u1 rcv Password snd p1 rcv root logged in snd CR rcv snd halt Script 7 FortiNet rcv login snd u1 rcv Password snd p1 rcv snd execute shutdown rcv Do you want to continue y n snd y Script 8 Symantec rcv login snd u1 rcv Password snd p1 rcv snd shutdown 54 ...

Страница 57: ...b key and the space key is distinguished respectively 8 A script continues after a start symbol 9 u1 corresponds to the user name 1 of a script shutdown page and u2 corresponds to the user name 2 p1 corresponds to the password of the user name 1 and similarly p2 corresponds to the password of the user name 2 cr refers that a user needs to press the enter key Example of a shutdown command Windows s...

Страница 58: ... User Limited Function Menu The access restriction to the function to each user is set up Before login After login 56 ...

Страница 59: ...admin 3 Limit User Name It is arbitrary and sets up ID of the user who wants to restrict a function 4 Limit User Password It is arbitrary and sets up the password of the user who wants to restrict a function 5 Select User Name No of the user who wants to set up the contents of concrete function restriction is specified 6 Limited Function Setting Only for Limited Users Enable Disable is chosen abou...

Страница 60: ... CO2 Setting Menu The result of having computed at estimate the carbon dioxide emissions of the apparatus whole connected to the uninterruptible power supply UPS is displayed Before login After login 58 ...

Страница 61: ... Trade and Industry and an environmental ministerial ordinance third number Data acquisition will be started if the acquisition period of a log is set up and an execution button is pushed After certain fixed period passed if an update button is pushed and being logged in the set up data of a period will be displayed 2 CO2 Log CO2 log for the past one month can be saved 3 Clear The log on a screen ...

Страница 62: ... Email Notification Menu The notice of E Mail of an uninterruptible power supply UPS state is set up Before login After login 60 ...

Страница 63: ...tatus Report AT hh mm When transmitting a daily status report from a SNMP Web card transmitting time is set up here 8 Mail Account This is the address of the mail notification destination 9 Description It is possible to indicate the information about an addressee as a memo 10 Mail Type The contents which transmit can be set up from the following four items for every addressee None It does not send...

Страница 64: ...an be performed By putting an external Web page and link a related Web page can be browsed easily For example you can easily access to the Web page in which technical support information is described or Web page of other uninterruptible power supply UPS in which the SNMP Web card is inserted Before login After login 62 ...

Страница 65: ... a screen 1 Screen Text A name given in this column is displayed under the link on the left hand side of a screen 2 LinkAddress URL of a link place is displayed and set up 3 Status Enable Disable of a link display is set up 63 ...

Страница 66: ...nfiguration screen UPS Extended Log Menu It is the log which summarized the operating state of the definite period of time of an uninterruptible power supply UPS The log of the maximum the minimum and average value of a definite period of time is taken about each parameter The time interval of acquisition can be set up on a SNMP Web card management SNMP Web card configuration screen UPS Events Log...

Страница 67: ...eliminates specific log data please click clear after putting a check beside object data 2 Save Log Data If it clicks each lower log data log data will download to a computer by CSV Please choose in advance Clear the corresponding log data Attention In the state that Clear the corresponding log data is set to Yes Log data associated will be deleted when any one of the links to each log data but it...

Страница 68: ...C input OFF after a power stop by schedule operation Off Off SNMP Web card Off 1 4 AC input restoration after the state of No 3 On Off SNMP Web card Off 5 UPS starting by schedule operation after the state of 4 On On SNMP Web card On 1 An uninterruptible power supply UPS is stopped by schedule operation and also when AC input is set to Off power supply to a SNMP Web card is stops but a schedule se...

Страница 69: ... of a SNMP Web card and choose the UPS management UPS control from an initial screen Next click Become Administrator and enter a user password as an administrator Next please choose the radial button on the right of a Shutdown Immediatly Then please click execute 67 ...

Страница 70: ...ution time of immediate shutdown 22 20 00 The setting conditions of a client computer Time required for the end of application software 30 sec Initial value 22 20 00 22 23 00 UPS ON UPS OFF Execution of immediate shutdown UPS stop 22 20 00 22 23 00 client computer ON client computer OFF Shutdown command OS stop Power OFF reception The end of waiting time Shutdown start 68 ...

Страница 71: ... of a SNMP Web card and choose the UPS management UPS control from an initial screen Next click Become Administrator and enter a user password as an administrator Next please choose the radial button on the right of a Restart UPS Then please click execute 69 ...

Страница 72: ...eboot Min 60 Reboot execution time 22 20 00 The setting conditions of a client computer Time required for the end of application software 30 sec Initial value 22 20 00 22 23 00 23 23 00 UPS ON UPS OFF Restart execution UPS stop UPS restart 22 20 00 22 23 00 23 23 00 client computer ON client computer OFF Shutdown command reception UPS stop restart The end of delay time Shutdown start 70 ...

Страница 73: ...rature Setup Steps 1 Please access the Web page of a SNMP Web card and choose the UPS management Shutdown setting from an initial screen Next click Become Administrator and enter a user password as an administrator Next please perform a setup required according to a day of the week Then please click Set Value For details please refer to a 19 page shutdown setting Menu 71 ...

Страница 74: ...S stop Sec 180 Initial value AC failure occurring time 22 20 00 The setting conditions of a client computer Time required for the end of application software 30 sec Initial value 22 20 00 22 30 00 22 33 00 UPS ON UPS OFF Warning sending by 30sec interval AC failure occurring The end of waiting time shutdown command sending to a client computer UPS stop 22 30 30 client computer ON client computer O...

Страница 75: ...e check that the date and time of a SNMP Web card are set up correctly Weekly Schedule Setup steps 1 Please access the Web page of a SNMP Web card and choose the UPS management Weekly Schedule from an initial screen Next click Become Administrator and enter a user password as an administrator Next please perform a setup required according to a day of the week Then please click Set Value 73 ...

Страница 76: ...een Please choose client shutdown UPS turn off from a column Shutdown actions and set up various time Next click Set Value Button The setting method of a schedule special day is the same as that of a schedule weekly Please set it by referring to the schedule week of described above 74 ...

Страница 77: ...tdown execution Mon 22 20 00 The reboot setting day of the week time Tue 9 00 00 The setting conditions of a client computer Time required for the end of application software 30 sec Initial value 22 10 00 22 20 00 22 23 00 09 00 00 Mon Mon Tue UPS ON UPS OFF Warning sending by 60sec interval The end of waiting time shutdown command sending to a client computer UPS stop UPS start 22 20 30 Mon Tue c...

Страница 78: ...wer supply UPS as a client Slave UPS will go into uninterruptible power supply UPS stop operation if the shutdown command from a master uninterruptible power supply UPS is received It can be used when managing the power supply of the apparatus storage in example which is not connected with a computer and a network as follows Configuration example Notes When failure event occurs shutdown command is...

Страница 79: ...upply UPS of one of them If the number of the power of two sets UPS of uninterruptible power supplies is one since generating simultaneously is assumed it is seldom necessary to be taken into consideration If it is another system please set up whether to shut down both or to shut down one according to a setup 3 The Web page of UPS management UPS remote shutdown on the slave uninterruptible power s...

Страница 80: ... registered as a client uninterruptible power supply UPS A master uninterruptible power supply UPS sends a shutdown command to a slave uninterruptible power supply UPS also when six events of a shutdown setting page occur A slave uninterruptible power supply UPS notify four items of failure event to a master uninterruptible power supply UPS except a schedule shutdown 78 ...

Страница 81: ...s of a Slave UPS Waiting time to a UPS stop Sec 300 The setting conditions of a client computer AC fail delay time 30 sec 22 20 00 22 30 00 22 33 00 Master UPS ON Master UPS OFF The input power failure occurs in the master UPS AC fail delay time is ends Shutdown command sending Master UPS stop 22 35 00 Slave UPS ON Slave UPS OFF Shutdown command reception Slave UPS stop 22 30 30 Client computer ON...

Страница 82: ... for more information 3 2 A setup of an SNMP trap addressee In order to set up an SNMP trap addressee it can perform from a SNMP Web card configuration Menu For more information please refer to the SNMP TRAP Receivers Menu of page 43 3 3 SNMP manager s setup Installation of MIB file Please add the Swc mib file in the MIB folder of CD ROM enclosed by this product to an SNMP manager s MIB database F...

Страница 83: ...og 4 2 The display of a monitoring screen At this monitoring screen log data is displayed by a line graph All the parameter data can be displayed on the same screen It can set up easily a display un displaying of each parameter 1 First please display the homepage of a SNMP Web card 2 In order to display the monitoring screen of an uninterruptible power supply UPS data log click Log at the upper ri...

Страница 84: ...rgin Right Display Margin Right Margin Scroll Bar Above The screen where six kinds of parametric expressions of Input Voltage V Output Voltage V Output Load Battery Capacity UPS Temperature degC and Input Frequency Hz were set up is illustrated The detail description of a screen 1 Display point Please click this option to display a log interval on a graph 2 Refresh Please choose this button when y...

Страница 85: ... is completed Left Display Margin Right Display Margin Right Margin Scroll Bar Above The screen where the display of Input Voltage V Output Voltage V Output Load Battery Capacity UPS Temperature degC and Input Frequency Hz is set up is illustrated The detail description of a screen 1 Display point Please click this option to display a log interval on a graph 2 Refresh Please choose this button whe...

Страница 86: ... is as follows Read public Read Write admin Community of read write and password are the same 2 The outline of a security setup When setting up a security level HTTP Security Control is first set as Enable from a setting menu by Telnet or serial connection after that By using Access Control Table on Telnet serial connection or access control on a Web screen the IP address which permits connection ...

Страница 87: ...erating temperature 0 40 Operating humidity 10 80 Supported UPS UPS BN50T BN75T BN100T BN150T BN220T BN300T BN50S BN75S BN100S BN150S BN220S BN300S BN75R BN150R BN300R BN100XR BN150XR BN240XR BU50SW BU75SW BU100SW BU150SW BU75RW BU100RW BU200RW BU300RW BU60RE BU100RE BU1002SW BU3002SW BU1002RW BU2002RWL BU3002RWL BU5002RWL Power consumption Maximum 3W Outside dimension 60 W 130 D 18 2 H mm Weight ...

Страница 88: ...ed ON OFF Unused OFF ON Unused OFF OFF Operation mode LED Port Green Yellow Operating state LAN Blink 1 sec OFF 100Mbps Ethernet traffic OFF Blink 1 sec 10Mbps Ethernet traffic OFF OFF Ethernet cutting Serial ON Blink 1 3sec RS 232 port active OFF Blink 1 sec Serial upgrade mode Mutual blink Mutual blink Automatic diagnosis mode ON ON Hardware error 86 ...

Страница 89: ...es Work procedure 1 The web browser of the Windows computer on the same network as SC20G2 is started and the IP address assigned to SC20G2 is inputted into an address bar following http Please carry out and push Input example When an IP address is a default 192 168 2 150 2 The initial screen of a SNMP Web card is displayed 87 ...

Страница 90: ...3 Please choose SNMP Web card management from the upper menu Then from a left menu please choose a SNMP Web card configuration and check that the item of network upgrade is enable 88 ...

Страница 91: ...r button SNMP Web card in the same network are displayed in the UPS List on 6 Please choose the displayed uninterruptible power supply UPS and click the Modify button Please enter login string information and a password and click the OK button 7 Click the OPEN button please choose the new firmware file used for upgrade and click it opens 8 Click the Upgrade button Then since the screen which check...

Страница 92: ...d on the same network is displayed on UPS List 3 Click the Discover button The SNMP Web card on the same network is displayed on UPS List 4 Please choose SC20G2 displayed and click the Modify button Please enter login string information and a password and click the OK button 5 Click the Acquire button Since the save screen of the configuration file of selected SC20G2 opens please save by arbitrary...

Страница 93: ... is reflected and click the Open button like the time of firmware upgrade If the dialog which opens a file is displayed the pull down menu written to be Binary Files bin will be clicked Please choose Config Files cfg from a list choose a configuration file to reflect in the next and click the button open 9 Click the Upgrade button A setup will be reflected if processing is completed and a message ...

Страница 94: ...ble 1 Please open a device manager from Control panel System and Security System 2 Please open the property of the adapter currently used from the tree of a network adaptor 3 Please open Power Management and check to Only allow a magic packet to wake the computer as shown in figure About the item which can be set up it is dependent on the version of a network adapter or a driver 92 ...

Страница 95: ...UPS reboot function to perform stop and starting of UPS Please check our homepage https www oss omron co jp ups for the newest product information Each company name and each company product name are the trademarks or registered trademarks of each company Carrying out unapproved reproduction of a part or all of the contents of this operation manual is forbidden It may change without a preliminary a...

Отзывы: