S8VK-WA
17
Connecting Stranded Wires
Use the following procedure to connect the wires to the terminal block.
1.
Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
The angle should be between 10° and 15°. If the flat-blade
screwdriver is inserted correctly, you will feel the spring in the
release hole.
2.
With the flat-blade screwdriver still inserted into the release hole,
insert the wire into the terminal hole until it strikes the terminal
block.
3.
Remove the flat-blade screwdriver from the release hole.
Checking Connections
• After the insertion, pull gently on the wire to make sure that it will
not come off and the wire is securely fastened to the terminal block
• The insulation distance is still satisfied although some of the
conductor may still be visible after being inserted into the terminal
block, even though recommended ferrules are used.
Removing Wires from the Push-In Plus Terminal
Block
Use the following procedure to remove wires from the terminal block.
The same method is used to remove stranded wires, solid wires, and
ferrules.
1.
Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
2.
With the flat-blade screwdriver still inserted into the release hole,
remove the wire from the terminal insertion hole.
3.
Remove the flat-blade screwdriver from the release hole.
Recommended Ferrules and Crimping Tools
Recommended Ferrules
S8VK-WA
@@@
24: Input Terminals/PE Terminals
S8VK-WA24024: DC Output Terminals
S8VK-WA
@@@
24:
Signal Output Terminals/COM Terminals
Note: 1.
Make sure that the outer diameter of the wire is smaller than
the inner diameter of the insulating sleeve of the
recommended ferrule.
2.
Make sure that the ferrule processing dimensions conform
to the following figure.
S8VK-WA48024: DC Output Terminals
Note: 1.
Make sure that the outer diameter of the wire is smaller than
the inner diameter of the insulating sleeve of the
recommended ferrule.
2.
Make sure that the ferrule processing dimensions conform
to the following figure.
Flat-
b
lade scre
w
dri
v
er
10° to 15°
1
3
2
Flat-
b
lade scre
w
dri
v
er
10° to 15°
1
3
2
Applicable
wire
Ferrule
Condu
ctor
length
(mm)
Stripping
length
(mm)
(Ferrules
used)
Recommended Ferrules
(mm
2
) (AWG)
Phoenix
Contact
Weid
muller
Wago
0.25
24
8
10
AI 0, 25-8
H0.25/12
FE-0.25-8N-YE
10
12
AI 0, 25-10
---
---
0.34
22
8
10
AI 0,34-8
H0.34/12
FE-0.34-8N-TQ
10
12
AI 0,34-10
---
---
0.50
20
8
10
AI 0,5-8
H0.5/14
FE-0.5-8N-WH
10
12
AI 0,5-10
H0.5/16
FE-0.5-10N-WH
0.75
18
8
10
AI 0,75-8
H0.75/14
FE-0.75-8N-GY
10
12
AI 0,75-10
H0.75/16
FE-0.75-10N-GY
1/1.25
18/17
8
10
AI 1-8
H1.0/14
FE-1.0-8N-RD
10
12
AI 1-10
H1.0/16
FE-1.0-10N-RD
1.25/1.5
17/16
8
10
AI 1,5-8
H1.5/14
FE-1.5-8N-BK
10
12
AI 1,5-10
H1.5/16
FE-1.5-10N-BK
2.5
14
10
12
AI 2, 5-10
H2.5/16DS
FE-2.5-10N-BU
Recommended crimp tool
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
PZ6 roto
Variocrimp4
Applicable
wire
Ferrule
Conduct
or
length
(mm)
Stripping
length
(mm)
(Ferrules
used)
Recommended Ferrules
(mm
2
) (AWG)
Phoenix
Contact
Weid
muller
Wago
4
12
12
14
AI 4-12
H4.0/20D FE-4.0-12N-GY
6
10
12
16
AI 6-12
H6.0/20
FE-6.0-12N-YE
*
Recommended crimp tool
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
PZ6 roto
Variocrimp4
*
Use the
Variocrimp16.
8 to 10 mm
2.6 mm max.
2.8 mm max.
12 mm
4 mm max.
4 mm max.