7
Specifications
Item
Product discontinuation Recommended replacement
Model
Model S8VS series
Model S8VK-G series
Model S8VK-C series
Input voltage
100 to 240 VAC
(allowable range: 85 to
264 VAC),
80 to 370 VDC
100 to 240 VAC,
90 to 350 VDC,
2-phase input from 3-phase source <240 VAC
Inrush
current
17.5 A max., 14 A typical
(for 100 VAC input) 35 A
max., 28 A typical (for
200 VAC input) * for a
cold start at 25°C
16 A (for 115 VAC
input), 32 A (for 230
VAC input) for cold start
at 25
q
C
40 A max (for 230
VAC input)
Start-up time
60 W 620 ms typical (for
100 VAC input) 400 ms
typical (for 200 VAC
input) 90 W 460 ms
typical (for 100 VAC
input) 300 ms typical (for
200 VAC input) 120 W
550 ms typical (for 100
VAC input) 400 ms typical
(for 200 VAC input)
15 W 520 to 580 ms
(for 115 VAC) 400 ms
(for 230 VAC), 30W
550 to 600 ms (for 115
VAC) 430 to 490 ms
(for 230 VAC), 60 W
570 to 650 ms (115
VAC) 430 to 500 ms
(230 VAC), 120 W 790
ms (for 115 VAC) 750
ms (for 230 VAC)
N/A
180 W 570 ms typical (for
100 VAC input) 470 ms
typical (for 200 VAC
input) 240 W 540 ms
typical (for 100 VAC
input) 230 ms typical (for
200 VAC input)
240 W 250 to 290 ms
(for 115/230 VAC
input); 480 W 290 ms
(for 115 VAC input) 260
ms (for 230 VAC input)
N/A
Output hold
time
60 W 34 ms typical (for
100 VAC input) 158 ms
typical (for 200 VAC
input) 90 W 28 ms typical
(for 100 VAC input) 132
ms typical (for 200 VAC
input) 120 W 52 ms
typical (for 100 VAC
input) 54 ms typical (for
200 VAC input)
15 W 28 to 32 ms (for
115 VAC) 34 to 138 ms
(for 230 VAC), 30 W 23
to 36 ms (for 115 VAC)
154 to 177 ms (230
VAC, 60 W 25 to 26 ms
(115 VAC) 129 to 139
ms (230 VAC), 120 W
42 ms (115/230 VAC)
N/A
180 W 58 ms typical (for
100 VAC input) 62 ms
typical (for 200 VAC
input) 240 W 64 ms
typical (for 100 VAC
input) 64 ms typical (for
200 VAC input)
240 W 44 ms (for
115/230 VAC) 480 W
40 ms (115 VAC) 50
ms (230 VAC)
N/A
Overload
protection
105% to 160% of rated
load current, Inverted L
voltage drop, Automatic
reset.
121% to 160% of rated
load current (130%
typical value)
Yes
Parallel
operation
No (However, backup
operation is possible. An
external diode is
required.)
Yes N/A
Operating
ambient
temperature
-10
q
C to +60
q
C -40
q
C to +70
q
C -25
q
C to 60
q
C
EMI
(Conducted
Emissions)
Conforms to EN6120-3
EN55011 Class B and
based on FCC Class A
Conforms to EN61204-
3 EN55011 Class B
and based on FCC
Class A
Conforms to
EN61204-3, EN55011
Class A