Wiring
•
Connect the ground completely. A protective earthing terminal stipulated in safety standards is used. Electric shock or malfunction may occur
if the ground is not connected completely.
•
Minor fire may possibly occur. Ensure that input and output terminals are wired correctly.
•
Do not apply more than 75-N force to the terminal block when tightening it.
•
Be sure to remove the sheet covering the Product for machining before power-ON so that it does not interfere with heat dissipation.
•
Use the following material for the wires to be connected to the S8VK-G to prevent smoking or ignition caused by abnormal loads.
Recommended Wire Type/Cross-sectional Area and Stripping Length
•
The wire insertion hole, and applicable screwdriver of the terminal block are as follows.
Precautions for Safe Use
INPUT
OUTPUT
PE
Wire Stripping
Length
Model
American
Wire Gauge
Solid Wire
/Stranded Wire
American
Wire Gauge
Solid Wire
/Stranded Wire
American
Wire Gauge
Solid Wire
/Stranded Wire
S8VK-G01505
AWG24 to 12
0.25 to 4 mm
2
/0.25 to 2.5 mm
2
AWG20 to 12
0.5 to 4 mm
2
/0.5 to 2.5 mm
2
AWG14 to 12
2.5 to 4 mm
2
/
2.5 to 4 mm
2
8 to 10 mm
S8VK-G01512
AWG22 to 12
0.35 to 4 mm
2
/0.35 to 2.5 mm
2
S8VK-G01524
AWG24 to 12
0.25 to 4 mm
2
/0.25 to 2.5 mm
2
S8VK-G03005
AWG24 to 12
0.25 to 4 mm
2
/0.25 to 2.5 mm
2
AWG18 to 12
0.75 to 4 mm
2
/0.75 to 2.5 mm
2
S8VK-G03012
AWG20 to 12
0.5 to 4 mm
2
/0.5 to 2.5 mm
2
S8VK-G03024
AWG22 to 12
0.35 to 4 mm
2
/0.35 to 2.5 mm
2
S8VK-G06012
AWG22 to 12
0.35 to 4 mm
2
/0.35 to 2.5 mm
2
AWG18 to 12
0.75 to 4 mm
2
/0.75 to 2.5 mm
2
S8VK-G06024
AWG20 to 12
0.5 to 4 mm
2
/0.5 to 2.5 mm
2
S8VK-G12024
AWG22 to 10
0.35 to 6 mm
2
/0.35 to 4 mm
2
AWG18 to 10
0.75 to 6 mm
2
/0.75 to 4 mm
2
AWG14 to 10
2.5 to 6 mm
2
/
2.5 to 4 mm
2
S8VK-G24024
AWG20 to 10
0.5 to 6 mm
2
/0.5 to 4 mm
2
AWG14 to 10
2.5 to 6 mm
2
/2.5 to 4 mm
2
S8VK-G24048
AWG18 to 10
0.75 to 6 mm
2
/0.75 to 4 mm
2
S8VK-G48024
AWG16 to 10
1.5 to 6 mm
2
/1.5 to 4 mm
2
AWG12 to 10
4 to 6 mm
2
/4 mm
2
S8VK-G48048
AWG14 to 10
2.5 to 6 mm
2
/2.5 to 4 mm
2
Model
Wire Insertion Hole
(Refer to the diagram on the right)
Applicable Screwdriver
W
L
No.
Driver Diameter
Length
S8VK-G01505
2.7
2.9
#1
3.5 mm max.
4.5 mm min.
S8VK-G01512
S8VK-G01524
S8VK-G03005
S8VK-G03012
S8VK-G03024
S8VK-G06012
S8VK-G06024
S8VK-G12024
2.9
#2
4.9 mm max.
10 mm min.
S8VK-G24024
S8VK-G24048
S8VK-G48024
S8VK-G48048
W
L