SIEPCYEUOQ2V01A Q2V Technical Manual
643
■
L2-04: Powloss Ramp Time@recovery
No.
(Hex.)
Name
Description
Default
(Range)
L2-04
(0488)
Powloss Ramp
Time@recovery
Sets the time for the drive output voltage to go back to correct voltage after completing speed
searches.
Determined by o2-04, C6-
01
(0.0 - 5.0 s)
Sets the time for voltage to recover from 0 V to the value set in
E1-05 [Max Output Voltage]
.
■
L2-05: UV Detection Lvl (Uv1)
No.
(Hex.)
Name
Description
Default
(Range)
L2-05
(0489)
UV Detection Lvl (Uv1)
Sets the voltage at which a
Uv1 [DC Bus Undervoltage]
fault is triggered or at which the KEB
function is activated. Usually it is not necessary to change this setting.
Determined by o2-04 and
E1-01
(200 V Class: 150 - 210 V,
400 V Class: 300 - 420 V)
NOTICE:
Damage to Equipment. When you set this parameter to a value lower than the default, you must install an AC reactor
on the input side of the power supply. If you do not install an AC reactor, it will cause damage to the drive circuitry.
Note:
If the low voltage detection level is near the lower limit value of
L2-05
, the drive will detect
Uv1
during KEB Ride-Thru operation. Do
not set the value too low when you use the KEB Ride-Thru function.
■
L2-06: KEB Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-06
(048A)
Expert
KEB Decel Time
Sets the deceleration time during KEB operation used to decrease the maximum output frequency
to 0.
0.0 s
(0.0 - 6000.0 s)
Set
L2-29 = 3 or 4 [KEB Method = System KEB1 Ride-Thru or System KEB2 Ride-Thru]
to enable this function.
When
L2-29 = 2 , 3, 4 [Single KEB2 Ride-Thru, System KEB1 Ride-Thru, System KEB2 Ride-Thru]
and you do
KEB Auto-Tuning, the drive will automatically set this value.
Sets the deceleration time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a
momentary power loss. If a
Uv1 [DC Bus Undervoltage]
fault occurs during KEB operation, decrease the
deceleration time. If an
ov [Overvoltage]
fault occurs, increase the deceleration time.
•
L2-06 = 0
The drive automatically decreases
C1-09 [Fast Stop Time]
to the base value to keep the DC bus voltage above
the low voltage detection level. The drive ignores
L2-02 [RideThrough Time@Power Loss]
in this condition.
•
L2-06 ≠ 0
As shown in
, the frequency reference decelerates to the KEB frequency level as specified by the
deceleration rate set in
L2-06
and then returns to the initial frequency reference as specified by
C1-01 [Accel
Time 1]
. The drive uses the setting value of the KEB frequency rate as shown in the this formula to set the KEB
frequency level:
KEB frequency level = Output frequency before power loss × (1 -
(L2-02)
/
(L2-06)
)
Figure 12.115 Kinetic Energy Backup Decel Time
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...