506
SIEPCYEUOQ2V01A Q2V Technical Manual
Table 12.25 Wiring Distance
Wiring Distance
50 mm (164 ft) Maximum
100 m (328 ft) Maximum
More than 100 m (328 ft)
C6-02 [Carrier Frequency Selection]
1 to F (up to 15 kHz)
1 to 2 (up to 5 kHz), 7
1 (up to 2 kHz), 7
Note:
•
When the wiring length is longer than 100 m (328 ft), set A1-02 = 0 [V/f Control].
•
The maximum wiring cable length between the drive and a PM motor is 100 m (328 ft).
•
If the cable length between the drive and the motor is too long when
A1-02 = 6
, set
A1-02 = 5
.
■
C6-03: Carrier Upper Frequency Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-03
(0225)
Carrier Upper Frequency
Limit
Sets the upper limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
(C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Setting a Fixed User-Defined Carrier Frequency
When you cannot use
C6-02
to set a carrier frequency between set selectable values, you can set the value in
C6-
03
. The carrier frequency will be fixed to the value set to
C6-03
.
When
A1-02 = 0 [Control Method = V/f Control]
, set
C6-03 = C6-04 [Carrier Lower Frequency Limit]
to fix the
carrier frequency.
Setting a Variable Carrier Frequency to Agree with the Output Frequency
When
A1-02 = 0
, set
C6-03
,
C6-04
, and
C6-05 [Carrier Freq Proportional Gain]
as shown in
to
make the carrier frequency change linearly with the output frequency.
Figure 12.47 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
•
When
C6-05 ≤ 7
, the drive disables
C6-04
. The carrier frequency is fixed to the value set to
C6-03
.
•
The drive detects
oPE11 [Carrier Frequency Setting Error]
when these conditions are correct at the same time:
–
C6-05 ≥ 6
–
C6-04 ≥ C6-03
■
C6-04: Carrier Lower Frequency Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-04
(0226)
Carrier Lower Frequency
Limit
Sets the lower limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
(C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Set
C6-03 [Carrier Upper Frequency Limit]
,
C6-04
, and
C6-05 [Carrier Freq Proportional Gain]
to make the
carrier frequency change linearly with the output frequency.
Note:
The drive detects
oPE11 [Carrier Frequency Setting Error]
when these conditions are correct at the same time:
•
C6-04 ≥ C6-03
•
C6-05 ≥ 6
■
C6-05: Carrier Freq Proportional Gain
No.
(Hex.)
Name
Description
Default
(Range)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection
= User (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(0 - 99)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...