152
SIEPCYEUOQ2V01A Q2V Technical Manual
Model
Terminal
Recommended Gauge
mm
2
Applicable Gauge
mm
2
Wire Stripping
Length
mm
Terminal Screw
Tightening Torque
N
∙
m (in
∙
lb)
2082
R/L1, S/L2, T/L3
35
10 - 50
20
M6
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3
25
10 - 35
20
M6
5 - 5.5
(45 - 49)
-, +1, +2
50
16 - 70
20
M6
5 - 5.5
(45 - 49)
B1, B2
16
4 - 16
10
M4
1.5 - 1.7
(13.5 - 15)
16
10 - 25
-
M6
5.4 - 6.0
(47.8 - 53.1)
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).
•
8-4NS from JST Mfg. Co., Ltd.
•
R8-4S from NICHIFU Co.,Ltd.
Single-Phase 200 V Class (CE-compliance)
Model
Terminal
Recommended Gauge
mm
2
Applicable Gauge
mm
2
Wire Stripping
Length
mm
Terminal Screw
Tightening Torque
N
∙
m (in
∙
lb)
B001
L/L1, N/L2
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
2.5
-
M3.5
0.8 - 1.0
(7.1 - 8.9)
B002
L/L1, N/L2
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
2.5
-
M3.5
0.8 - 1.0
(7.1 - 8.9)
B004
L/L1, N/L2
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
2.5
2.5
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
2.5
-
M3.5
0.8 - 1.0
(7.1 - 8.9)
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...