![Omron Q2A Series Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/omron/q2a-series/q2a-series_manual_742788023.webp)
Q2A
23
B
Option cards
C
Accessories
D
Computer software
Type
Model
Description
Function
Communicat
ion
o
p
ti
on ca
rds
SI-ES3
EtherCAT
• Used for running or stopping the inverter, setting or referencing parameters, and
monitoring output frequency, output current, or similar items through EtherCAT com-
munication with the host controller.
SI-EM3
Modbus TCP/IP
• Used for running or stopping the inverter, setting or referencing parameters, and
monitoring output frequency, output current, or similar items through Modbus TCP/IP
communication with the host controller.
SI-EM3/D
Modbus TCP/IP Dual-Port
SI-EP3
PROFINET
• Used for running or stopping the inverter, setting or referencing parameters, and
monitoring output frequency, output current, or similar items through PROFINET
communication with the host controller.
SI-EN3
EtherNet/IP
• Used for running or stopping the inverter, setting or referencing parameters, and
monitoring output frequency, output current, or similar items through EtherNet/IP
communication with the host controller.
SI-EN3/D
EtherNet/IP Dual-Port
SI-EL3
POWERLINK
• Used for running or stopping the inverter, setting or referencing parameters, and
monitoring output frequency, output current, or similar items through POWERLINK
communication with the host controller.
Inpu
t/
out
pu
t
opt
ion
car
d
s
AI-A3
Analog input
• To configure very accurate analog references at high resolution
Input signal level: -10 to 10 VDC (20 k
Ω
) at 4 to 20 mA (250
Ω
)
Input channel: 3 channels (use a DIP switch to select voltage or current input)
Voltage input resolution: 13 bits (1/8192) + encoding
Current input resolution: 1/4096
AO-A3
Analog monitor
• To use analog signals to monitor the drive output frequency and current
Output resolution: 11 bits (1/2048) + encoding
Output voltage: -10 to 10 VDC (non-insulated)
Output channel: 2 channels
DI-A3
Digital input
• To use digital speed references and MFDI with a maximum 16 bits of resolution
Input signals: Binary, 16 bits: BCD4 SIGN SET signal (use parame-
ters to select 6 bits, 8 bits or 12 bits)
Input voltage: 24 V (insulated)
Input current: 8 mA
DO-A3
Digital output
• To output insulated digital signals and monitor the operation status of the drive (alarm
signals and detecting zero speed)
Photocoupler relays: 6 channels (48 V, 50 mA max.)
Relay contact: 2 channels (250 VAC at 1 A or less, 30 VDC at 1 A or less)
Feedb
ack speed
o
p
ti
on cards
PG-B3
*
1
*
1. This option card can only be used with CL-V/f and OLV control methods.
Motor PG feedback open
collector interface
• For speed feedback input by connecting a motor encoder
Input: 3 track (one or two tracks), for HTL encoder connection, 50 KHz max
Output: 3 track, open collector
Encoder power supply: 12 V, 200 mA max
PG-X3
*
2
*
2. This option card can only be used with CLV, CL-V/f and CLV/PM control methods.
Motor PG feedback line driver
interface
• For speed feedback input by connecting a motor encoder
Input: 3 track (one or two tracks), line driver, 300 kHz max
Output: 3 track, line driver
Encoder power supply: 5 V or 12 V, 200 mA max
PG-F3
*
3
*
3. This option card can only be used with CLV/PM control method.
EnDat encoder
• For speed feedback input by connecting a motor encoder
Encoder type: EnDat 2.1/01, EnDat 2.2/01, EnDat 2.2/22 (HEIDENHAIN), HIPER-
FACE models (SICK STEGMANN)
Maximum input frequency: 20 kHz
Pulse monitor: Equivalent to RS-422 level
Output voltage: 5 V at max. current of 330 mA, 8 V at max. current of 150 mA
Wiring length: 20 m max. for the encoder, 30 m max. for the pulse monitor
PG-RT3
*
4
*
4. This option card can only be used with CLV and CLV/PM control methods.
Resolver interface
• For motor speed feedback by connecting a resolver (TS2640N321E64 by Tamagawa
Seiki Co., LTD)
Input voltage: 10 VAC rms 10 kHz
Transformation ratio: 0.5±5%
Maximum input current: 100 mA rms
Description
Functions
Model
USB cable
Mini USB to USB cable
AX-CUSBM002-E
Remote operator cable
3 meters cable to connect the keypad and drive
3G3AX-CAJOP300-EE
Keypad mounting bracket
This bracket is required to mount the LCD Remote
Operator outside an enclosure panel
Screw type
900-192-933-001
Nut type
900-192-933-002
Description
Functions
Model
Computer software
Software tool to configure drives and manage parameters
Q2edit
Software tool to do advanced drive programming
Q2dev
I175E-EN-01+Q2A+Datasheet.fm Seite 23 Montag, 26. März 2018 3:18 15