Frequency inverters
Standard connections
*1.
When you install a DC reactor, you must remove the jumper between ter1 and +2.
*2.
Models 4060 to 4675 have a DC reactor.
*3.
Connect peripheral options to terminals -, +1, +2, B1 and B2.
*4.
Use only SOURCE Mode for Safe Disable input.
*5.
Disconnect the wire jumper between H1 and HC, and H2 and HC to use the Safe Disable input.
Installation
Q2A
Main circuit
Braking resistor
(option)
U
X
Short bar
DC reactor (option)
*1
*3
+2
+1
B1
B2
-
Option card connector
CN5-C
CN5-B
CN5-A
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Control circuit
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
D0V
DIC
D24V
+24 VDC
GND
Shield ground terminal
PI
Pulse train input
(max. 32 kHz)
+10V
Power supply 10.5 VDC
(max. 20 mA)
AI1
Analog input 1(Frequency reference)
-10 to +10 VDC (20 k
) / 0 to 10 VDC (20 k
)
0 to 20 mA (250
) / 4 to 20 mA (250
)
AI2
Analog input 2 (Frequency reference bias)
-10 to +10 VDC (20 k
) / 0 to 10 VDC (20 k
)
0 to 20 mA (250
) / 4 to 20 mA (250
)
AI3
Analog input 3/PTC input
(Auxiliary frequency reference)
-10 to +10 VDC (20 k
) / 0 to 10 VDC (20 k
)
0 to 20 mA (250
) / 4 to 20 mA (250
)
A0V
-10V
E24V
RS485+
RS485-
A0V
H1
H2
HC
D0V
Power supply, -10.5 VDC, max. 20 mA
Power supply input 24 VDC
Termination resistor
(120
, 1/2 W)
DIP switch S2
PG-B3
TB1
A+
A-
B+
B-
Z+
Z-
SD
FE
TB2
IP
IG
AO
IG
BO
IG
ZO
IG
1NO
1NC
1CM
2NO
2CM
3NO
3CM
4NO
4CM
PO
A0V
0 V
0 V
0 V
0 V
GND
AO1
AO2
AOV
DIP switch S2
Termination resistor ON/OFF
Jumper switch S5
Analog monitor voltage/
current (V)
DIP switch S4
AI3 analog input/
PTC input (AI)
DIP switch S1-3
AI3 voltage/
current (V)
DIP switch S1-2
AI2 voltage/
current (I)
DIP switch S1-1
AI1 voltage/
current (V)
V
I
FM AM
V
I
V
I
V
I
AI
PTC
OFF
ON
FU
FV
FW
Cooling
fan
M
r1
s1
t1
U
V
W
M
Shielded wire
PG
Monitor signal (phase A)
B pulse monitor signal
Fault relay output:
250 VAC, max. 1 A
30 VDC, max. 1 A
(min. 5 VDC, 10 mA)
MFDO (During Run):
250 VAC, max. 1 A
30 VDC, max. 1 A
(min. 5 VDC, 10 mA)
MFDO (Zero Speed):
250 VAC, max. 1 A
30 VDC, max. 1 A
(min. 5 VDC, 10 mA)
MFDO (Speed Agree 1):
250 VAC, max. 1 A
30 VDC, max. 1 A
(min. 5 VDC, 10 mA)
Pulse train output
(Output frequency):
0 to 32 kHz (2 k
)
FM
AM
Multi-function analog monitor output 1
(Output frequency):
-10 to +10 VDC / 0 to 10 VDC / 4 to 20 mA
Multi-function analog monitor output 2
(Output current):
-10 to +10 VDC / 0 to 10 VDC / 4 to 20 mA
Identifies shielded cable
Identifies shielded twisted-pair cable
Identifies main circuit terminal
Identifies control circuit terminal
Three-phase
power supply
400 V,
50/60 Hz
R
S
T
RCM/RCD
2MCCB
Fuse
MC
r1
s1
t1
MC
MB 2MCCB THRX OFF ON
MC
MC
SA
THRX
THRX
SA
SA
1
2
Braking resistor unit
Thermal overload relay
MC
MA
TRX
Fault relay
Multi-function
Digital Input
Default setting
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
JOG command
External baseblock
Multi-step speed 1
(Main/Aux switch)
Multi-step speed 2
Power supply output
DC 24 V, max. 150 mA
Frequency
Bias
Pulse train input
0 to 10 VDC
4 to 20 mA
0 to 10 VDC
2 k
Frequency
setting
potentiometer
24 VDC control
power supply input
24 V, 700 mA
MEMOBUS
RS-485
Max. 115.2 kbps
Safety
switch
Open
Connect to MFDO
Safety
controller
Reset/
feedback
input
S2
S1
Safety Electronic
Device Monitor output
Safe Disable input
*4
Wire jumper
*5
*2
I175E-EN-01+Q2A+Datasheet.fm Seite 14 Montag, 26. März 2018 3:18 15