4-4-3
Selecting Protective Devices
This section describes how to select protective devices (e.g., breakers and fuses) to protect against
short circuits and overcurrents in external circuits.
Overcurrent is the current that flows when an excessive load is connected and one of the following
ratings is exceeded.
Unit
Item for rating
Rated value
CPU Unit
NX Unit power supply capacity
10 W max.
Current capacity of power supply
terminal
4 A max.
Additional NX Unit Power Supply Unit
NX Unit power supply capacity
Refer to
the NX-series System Units User’s
Manual
(Cat. No. W523).
Current capacity of power supply
terminal
Additional I/O Power Supply Unit
Maximum I/O power supply current
.
Current capacity of I/O power sup-
ply terminals
*1.
Even if the model of the Additional I/O Power Supply Unit you use allows the maximum I/O power supply current or current
capacity of the I/O power supply terminals which is greater than 4 A, the I/O power must be supplied at 4 A or less be-
cause of the restriction on the CPU Rack system configuration.
The built-in I/O overcurrent refers to a current that flows when the maximum switching capacity of the
built-in output is exceeded.
Precautions for Safe Use
Use the I/O power supply current for the CPU Rack of the NX1P2 CPU Unit at 4 A or less. Us-
ing the currents that are outside of the specifications may cause failure or damage.
Selecting Protective Devices
Consider the following items when you select protective devices.
• Protective device specifications (breaking/fusing, detection characteristics, steady current value,
etc.)
• Inrush current when power is turned ON
• Inrush current when connected external devices turn ON and OFF*1
*1. Refer to
4-3-5 Restrictions on Inrush Current for ON/OFF Operation
on page 4-21 for information on the in-
rush current when connected external devices are turned ON and OFF.
For the breaking/fusing time, use protective devices that meet the conditions in the following table.
l
For Unit Power Supply
Current
Breaking/fusing
time
6 A
1 min max.
12 A
15 s max.
21 A
5 s max.
30 A
2.5 s max.
4 Designing the Power Supply System
4-25
NX-series NX1P2 CPU Unit Hardware User’s Manual (W578)
4-4 Selecting External Power Supplies and Protective Devices
4
4-4-3
Selecting Protective Devices
Содержание NX1P2 series
Страница 8: ...Manual Structure 6 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 52: ...Revision History 50 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 82: ...2 System Configuration 2 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 170: ...a b Flat blade screwdriver 1 2 5 Installation and Wiring 5 26 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 174: ...4 Close the Memory Card cover 5 Installation and Wiring 5 30 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 176: ...4 Close the Memory Card cover 5 Installation and Wiring 5 32 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 224: ...0 4 mm Side view Front view 2 5 mm 5 Installation and Wiring 5 80 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 258: ...Appendices A 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 259: ...I Index I 1 NX series NX1P2 CPU Unit Hardware User s Manual W578 I...
Страница 262: ...Index I 4 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 263: ......