6 - 7
6 Types and Functions of IO-Link Master Units
NX-series IO-Link Master Unit User’s Manual (W567)
6-
3 Li
st
of
Se
tti
n
gs
6
6-3
List of Settings
The followings are the setting descriptions, setting ranges, and default values of the functions that can
be used in the IO-Link Master Unit.
The settings are reflected after the Unit is restarted.
Precautions for Safe Use
The Unit is restarted after the Unit operation settings are transferred from the Support Software.
Always sufficiently check the safety at the connected devices before you transfer the Unit oper-
ation settings.
Setting
Description
Default value
Setting range
Index
Subindex
IO-Link Device Verifica-
tion Setting
This setting specifies whether to
verify that the IO-Link devices
actually connected to the ports
match the IO-Link devices in the
IO-Link Device Configuration
Settings when IO-Link communi-
cations start.
00 hex: Disabled
00 to 02 hex
00 hex: Do not
check.
01 hex: Verify the
vendor ID, device ID,
and IO-Link revision.
02 hex: Verify the
vendor ID, device ID,
and IO-Link revision
serial number.
5001 hex
01 to 04
hex
IO-Link
Device
Configu-
ration
Set-
tings
*1
Device ID
The type of IO-Link device.
00000000 hex
00000000 to
00FFFFFF hex
5006 to
5009 hex
01 hex
Vendor ID
The vendor ID of the IO-Link
device.
00000000 hex
00000000 to
0000FFFF hex
02 hex
Serial Num-
ber
The serial number of the IO-Link
device.
---
16 characters max.
05 hex
IO-Link Revi-
sion
*2
The IO-Link revision of the
IO-Link device.
• Set the major revision in the 4
upper bits, and the minor revi-
sion in the 4 lower bits.
00 hex
00 to FF hex
06 hex
IO-Link Input
Data Size
*3
The size (in bytes) of the IO-Link
process input data from the
IO-Link device.
02 hex (2 bytes)
00 to 20 hex (0 to 32
bytes)
09 hex
IO-Link Out-
put Data
Size
*4
The size (in bytes) of the IO-Link
process output data to the
IO-Link device.
02 hex (2 bytes)
00 to 20 hex (0 to 32
bytes)
0A hex
Master Con-
trol Commu-
nications
Mode Setting
Set the communications mode
for each port.
03 hex: IO-Link
Mode
00 to 03 hex
00 hex: Disable Port
01 hex: SIO (DI)
Mode
02 hex: SIO (DO)
Mode
03 hex: IO-Link
Mode
0B hex
Backup Setting
Make this setting to back up the
parameter settings of the IO-Link
devices in the IO-Link Master
Unit.
Specify whether to enable or dis-
able backup for each port.
00 hex
00 to 01 hex
00 hex: Disables
backup
01 hex: Enables
backup
5002 hex
01 to 04
hex
Содержание NX-ILM400
Страница 12: ...Manual Structure 10 NX series IO Link Master Unit User s Manual W567...
Страница 36: ...Revision History 34 NX series IO Link Master Unit User s Manual W567...
Страница 38: ...Sections in this Manual 36 NX series IO Link Master Unit User s Manual W567...
Страница 52: ...2 Specifications 2 4 NX series IO Link Master Unit User s Manual W567...
Страница 58: ...3 Part Names and Functions 3 6 NX series IO Link Master Unit User s Manual W567...
Страница 120: ...7 Troubleshooting 7 8 NX series IO Link Master Unit User s Manual W567...
Страница 126: ...8 Inspection and Maintenance 8 6 NX series IO Link Master Unit User s Manual W567...
Страница 170: ...Appendices A 44 NX series IO Link Master Unit User s Manual W567...
Страница 171: ...I 1 I NX series IO Link Master Unit User s Manual W567 Index...
Страница 174: ...I 4 NX series IO Link Master Unit User s Manual W567 Index...
Страница 175: ......